Laserfiche WebLink
Hazardous Waste Tank System June <br /> Written Assessment per CCR Title 22 <br /> Zoom Car Wash 3434 East Hammer Lane Stockton, CA 95212 2019 <br /> Volume calculation(s) <br /> • The used oil tank has integral secondary containment. <br /> • The waste antifreeze drum requires secondary containment. <br /> • The used oil piping is indoors within the lube bay pit. <br /> The lube bay pit has a volume of 59,000 gallons. The pit is indoors. Rain is not a <br /> factor. The largest tank is 1,000 gallons. The containment is sufficient <br /> Visual inspection of containment area: <br /> The lube pit was dry. The concrete was free of cracks and gaps and is <br /> reasonably impermeable. <br /> weekry JST kaspacken Lag <br /> I <br /> L l <br /> Figure 12 <br /> Lube bay inspection check sheet. Tank has not had a daily inspection in 8 weeks <br /> Site Security: The waste oil tank and waste antifreeze drum are within locked <br /> areas. The site has 24-hour surveillance and the area is routinely patrolled by the <br /> Stockton Police. <br /> Secondary Containment findings: The secondary containment system is of <br /> sufficient capacity and condition for the containment of releases from all tanks <br /> and ancillary equipment. Initials: <br /> Strandberg Associates 1(866) 388-0404 rwaterquy(c)rwaterquy.com 17 <br />