Laserfiche WebLink
TTSiats4fdty 'Tam Testing Systems, Inc <br /> j J rt <br /> i <br /> • - R ! # PTI 12 55 June 7 , 1990 <br /> Mr. Jim Langston <br /> Lanaston'S <br /> P. 0. Box 97 Site: 15615 South 7th St. <br /> Lathrop, California 95330 Lathrop, California <br /> Dear Mr. Langston: <br /> Following is a summary of the precision testing we <br /> recently conducted on your underground storage tank(s) - <br /> Enclosed are copies of the test worksheets and computer <br /> generated data for your submittal to the appropriate <br /> governmental agency. <br /> I <br /> A tank system may be considered tight, according to the <br /> current regulations if the the teat results shown below do <br /> not exceed 0 .05 gph. If the results are beyond this <br /> parameter, an unauthorized release may have occurred, and <br /> you should consider taking remedial action- <br /> . TANK # OR TANK PRODUCT TEST WITHIN TIGHT <br /> LOCATION CAPACITY CONTAINED RESULTS TANK PARILMETERS <br /> Center 41000 Reg Gas -.066 Beyond Parameter <br /> Please contact us if you need additional assistance or <br /> information. <br /> Sincerely, <br /> fJ r <br /> Since <br /> Keser <br /> Certified T er <br /> 804 262-8378 166 FYtmX West Circle Stockton, CA 95206 (210 6-8036 <br />