Laserfiche WebLink
_ LDT 5000 Field Test Apparatus Page 1 of 1 <br /> Tanknology Line Leak Detector Test <br /> Work Order: 2344631 Date: 4/23/2020 <br /> Site Name/ID: 7-Eleven 38153/38153 <br /> Address: 121 S. Center Street <br /> City: Stockton State: CA Zip: 95202 <br /> Tank IDTi:REGULAR UNLEADED 2:PREMIUM UNLEADED T3:DIESEL <br /> Product REG UNLEAD PREMIUM Diesel <br /> Product Line 1 1 1 <br /> Tested From 3 3 3 <br /> Existing/New Existing Existing Existing <br /> Mechanical/Electronic Mechanical Mechanical Mechanical <br /> Manufacturer/Model Vaporless LD-2000 Vaporless LD-2000 Vaporless LD-200 <br /> erial No. 1809339 18091340 18091338 <br /> Pump Operating Pressure(psi) 38.00 29.00 30.00 <br /> Calibrated Leak(ml/min) 189.0 189.0 189.0 <br /> Calibrated Leak(gph) 3.00 3.00 3.00 <br /> Holding PSI 38.00 29.00 31.00 <br /> N/A for Electronic Lo's <br /> Resiliency(ml) 190.00 170.00 170.00 <br /> N/A for Electronic Lo's <br /> Metering PSI 16 15 20 <br /> N/A for Electronic Lo's <br /> Opening Time(sec) 3 6 3 <br /> 'NIA for Electronic LD's <br /> Test Results Pass Pass Pass <br /> Technician Comments: <br /> Technician Name: Erik Mcallister Certification#: 149537 <br /> � <br /> Technician Signature: Expire Date: 5/12/2022 <br /> Environmental Compliance for Petroleum Systems <br /> ©2020 Tanknology Inc.,Austin,TX All rights reserved. tanknology.com <br />