Laserfiche WebLink
�- San Joaquin Valley <br /> K <br /> Air Pollution Control District <br /> PERMIT UNIT: NEXPIRATION DATE: 03/3112007 <br /> EQUIPMENT DESCRIPTION: <br /> j 1200 BHP CATERPILLAR, MODEL CAT T349D, DIESEL FIRED EMERGENCY STANDBY iC ENGINE (#1) SERVING AN <br /> ELECTRICAL GENERATOR. <br /> PERMIT UNIT REQUIREMENTS. <br /> f 1. Particulate matter emissions shall not exceed 0.1 grains/dscf in concentration. [District Rule 42011 <br /> ti <br /> 2. The engine shall be operated only for maintenance. testing, and required regulatory purposes, and during emergency <br /> { situations. operation of the engine for maintenance, testing, and required regulatory purposes shall not exceed 200 <br /> -hours per year. [District NSR Rule and District Rule 4701] <br /> 1 The permittee shall maintain records of hours of non-emergency operation and of the sulfur content of the diesel, fuel <br /> 'used. Such records shall be made available for District inspection upon request for a period of two years. [District <br /> Rule 1070] <br /> i <br /> t <br /> k <br /> These terms and conditions are part of the Facility-wide Permit to Operate. <br /> i; <br /> FacilityName: CALIFORNIA STATE UNlVEFt51TY I,. <br />