Laserfiche WebLink
S (7 (1 Environmental Health Department <br /> --- U IN <br /> C0UUUNTY— <br /> TABLE #2 RECOMMENDED MINIMUM VERIFICATION ANALYSES <br /> FOR UNDERGROUND STORAGE TANK INVESTIGATIONS <br /> TANK TANK Gasoline Diesel BTEX VOCsttl Semi- pit & PCB Total Title 22 <br /> # CONTENTS VOCslzt Grease Lead Metals(3) <br /> 8015M 8021B 82606 8082 7421 <br /> 82608 8015M 82608 8270C 16G4A <br /> Unknown Fuel X X X X <br /> (C4-C36) <br /> Gasoline <br /> (C4-C20) X X X <br /> Diesel <br /> (C10—C36) X X X <br /> Jet Fuel/Kerosene <br /> (Cg-C20) X X <br /> Heating Oil <br /> (C10-C32) X X ',.... <br /> Stoddard Solvent <br /> (non-chlorinated) X X <br /> Chlorinated <br /> Solvents X X <br /> Waste Oil or <br /> Unknown Contents X X X X X X X <br /> Notes : <br /> 1 . EPA Method 8260B analyses must include all analytes listed in the method plus fuel oxygenates <br /> methyl-tertiary-butyl ether (MTBE), diisopropyl ether (DIPE) , ethyl-tertiary-butyl ether (EtBE) , <br /> tertiary-amyl-methyl ether (TAME), tertiary-butanol (TBA) , methanol and ethanol and fuel additives <br /> 1 ,2-dichloroethane (1 ,2-DCA) and ethylene dibromide (EDB or 1 , 2-dibromoethane) , <br /> I If pentachlorophenol (PCP) is identified , analyze the soil and/or water sample for dioxins and <br /> furans by EPA Method 8290 and pesticides by EPA Method 8081A <br /> 3. Title 22 Metals: Method 601013 may be used for all but the following metals , for which individual AA <br /> methods are required: Antimony & Arsenic by 7062 , Cadmium by 7131A, Lead by 7421 , Mercury by <br /> 7471A, Nickel by 7521 , Selenium by 7742 , and Thallium by 7841 . <br /> 4. Non-proprietary, performance based analytical methods may be used with approval of Regional <br /> Board staff. <br /> 7 of 10 <br />