Laserfiche WebLink
Hazardous Waste Tank System December <br /> Preliminary Written Assessment per CCR Title 22 <br /> Chase Chevrolet quick Lube Stockton,CA 95212 2013 <br /> Volume calculation(s) <br /> The waste oil tank has integral secondary containment. <br /> Both the waste oil tank and waste antifreeze tank are within the Quick Lube <br /> service vault which provides secondary containment for tanks, pumps and piping. <br /> The vault's volume is 48' x 28' x 7.5' = 10,080 ft3 which equals 75,398 gallons. <br /> The largest tank is 1,500 gallons. The secondary containment is sufficient. <br /> Visual inspection of containment area: <br /> Inspection of the service vault found it free of cracks, spalling, gaps or other <br /> damage. The concrete is painted with epoxy paint which makes it reasonable <br /> impermeable. <br /> Site Security: The waste oil and waste antifreeze tanks are within locked areas. <br /> The area has a security system and is locked when not attended. The area is <br /> routinely patrolled by the Stockton Police. <br /> Secondary Containment findings: The secondary containment syste is of <br /> sufficient capacity and condition for the containment of releases from all s <br /> and ancillary equipment. Initials: <br /> RECEIVED <br /> APP 2 5 2014 <br /> ENVIRONMENTAL <br /> HEALTH DEP <br /> Strandberg Associates 1(866) 388-17404 EAaterquy@rwaterquy.com 27 <br />