Laserfiche WebLink
TANKNOL0GY - UNDERGROUND LEAK DETECTION SYSTEM - (V3.12) Page 8 <br />SHELL ` H0U9203-lN910623-46735- 1 - Mar 04' l?92/ 23/08 <br />%"y 01 No: t.J--- -7- F"L (0 -T- mw sw w 1F3 ILJ 01 F-1 oil FLA� <br />TEST DATE : Mar 04, 1992 <br />START TIME : 23:08:44 <br />CLIENT : SHELL <br />LOCATION NAME : SHELL <br />LOCATION CODE : 7524-3505 <br />TANK <br />CONFIGURATION <br />i Tandem <br />TANK <br />CONTENTS <br />: S/R/UNL <br />TANK <br />NUMBER <br />: 01 <br />TANK <br />DIAMETER <br />: 94 <br />TANK <br />CAPACITY <br />: 10000 <br />TANK <br />MANUFACTURER <br />: <br />TANK <br />MATERIAL <br />: Steel <br />TANK <br />REGISTRATION # <br />: <br />TANK <br />DATE INSTALLED <br />INITIAL DIPPED FUEL LEVEL : 77.00 <br />INITIAL DIPPED WATER LEVEL : 0.00 <br />POST PUMPING WATER LEVEL : 0.0O <br />S/UNL <br />02 <br />94 in <br />10000 6 <br />Steel <br />78.00 in <br />0.00 in <br />0.00 in <br />-�o!2,h p-N-1K� 7- FE: f=3 _T_ F07 EFT 1=3KJK_-T_ <br />TEST INITIAL WATER LEVEL : 0.00 0.00 in <br />TEST FINAL WATER LEVEL : 0.00 0.00 in <br />NATER INGRESS : 0.00 0.00 in <br />BUBBLE SIGNATURES : No <br />VACU-TECT TEST RESULT <br />COMMENTS: <br />CONCLUSION: S/R/UNL AND S/UNL TANKS TESTED TIGHT. <br />LINE <br />#1 Passed <br />#2 <br />#3 <br />#4 <br />#5 <br />#6 <br />COMMENTS: <br />1L_1 01 E=7 -FF E-:-_!ff3 -Y- LJ P_ -T_ <br />TEST RATE <br />PRESSURE_ <br />50 PSI 0.00 GPH Passed <br />CONCLUSION: SIR/UNL AND S/UNL LINES TESTED TIGHT. <br />` <br />This test us cundLicted in occmdame with U.S. EPP. Ru}e 40 �� Parts 280 aid 281. <br />TEST RATE <br />ENRES39UFRE LOSS <br />50 PSI 0.00 GPH <br />0 ACU-TECT(tm) Test Number <br />