Laserfiche WebLink
71 <br /> IT <br /> `TS <br /> Integrity Tank Testing Systems, Inc. <br /> nacc <br /> AUG <br /> 0 41988 <br /> ENVIROMENTAL HEALTH <br />' F ERM-UsERVICES <br /> TEST DATA AND <br /> TEST RESULTS <br /> February 15 , 1988 <br /> Mr. Jim Blais <br /> Lodi Memorial Hospital„ <br /> 75 South Fairmont Avenue . <br /> -od.i , California 95240 <br /> Dear Mr. Blais : <br /> Following is a summary of the precision testing we recently <br /> C-011ducted on your underground storage tank(s) . <br /> Enclosed are copies or the test worksheets and graphs gene- <br /> rr c.cd for your submittal *c, the appropriate governrien tall agc�ncv . <br /> A `_,II1°'_ system is considered tight , according t`.> the ctirrnnt <br /> Les , i_t` the gain is less than . 02 or the loss :z_,• j,.- . 05 <br /> _ons per one hour of testing. If the results are +- eyond thea;:_ <br /> yoti il-:3uld con—cider taking some remed:� <br /> dal. actior, . <br /> TANK r-jtODITCT TEST WLTifI1' TIGPl. <br /> i:Ut:Al :ON A1'At I T Y CONTAINED RESULTS TANK T ARAME 'FRS <br /> North 1,000 U/1, Gas -. 02952 Yes <br /> Please contact us if you need additional assistance or <br /> i'-).1.orInat i011. <br /> Sinc,.e—rely , <br /> e r <br /> Ccr_ tifio ''' ester <br /> 800 262-8378 166 Frank "east Circle Stockton., CA 95206 (209) 466-8036 <br />