Laserfiche WebLink
Idams <br />Uorecislon <br />Unsfir umentation, Co. <br />3031 TISH WAY, SUITE 200 * SAN JOSE, CAUFORNIA 95128 <br />(408) 244-6739 & FAX (408) 244-6801 <br />ARCO Products Company <br />API/Ronan X76S Leak Detection Certification <br />Facility # 2/3: Date 211-2�1 9�_ <br />Address.- 2q0,?&(AV1A.140* <br />vas/ V. <br />I Verify Intrinsicr Safety <br />Proper field wire termination <br />Proper power wiring with earth ground and individual breaker <br />Complete isolation of I.S. field wiring from any other wiring <br />especially in gutters <br />vol"'Proper use of E.Y.S. fittings <br />II. Check for proper panel installation <br />V-* -Panel mounted in a nonhazardous location <br />v,"'Panel is accesible to station operators <br />v""All field wiring is labelled at terminal 'strip or adjacent gutter <br />All wiring to panel is brought through appropriate punch -outs <br />III Check for proper probe installation <br />ve"Piping sump sensors suspended within one inch of sump bottom <br />Double walled FRP tank sensors(LS-7) installed at bottom of tank <br />with a pull wire circumventing the primary tank and accessible <br />from grade. <br />Annular space risers should be sealed watertight with field <br />wiring penetrating using cable grips or other apprpriate method <br />✓ Probe leads terminating in a watertight J -box <br />IV Check system operation <br />✓ Verify proper fuctioning of alarm horn and lights by pushing <br />the test button <br />