03/12/99 16:31 FAX 425 251 8782 BARCHAUSEN U021/029 <br /> MoArn Welding Companp, Inc. <br /> PO Box 1450 - <br /> i e <br /> icdes NaHonwkie - (SID2)685-"00 <br /> LONG FORM: Section 13215 <br /> Guido SpeciGeation GLASTEEL H <br /> Modern WeWing Company,Inc <br /> GI.&TrEEL 11, S-13, FRP Jacketed Steel <br /> Underground Storage Tank PART 11 Products <br /> PART I General 2.01 GLASTEEL 11 Underground Storage Tanks <br /> 1.01 Related Work Specified in Other Sections A- Loadmg Canditions: Tanks shall meet the <br /> following design criteria. <br /> A Cast-in-Place Concrete: Section 03300 1.Surface Loading: When installed according to <br /> B_ Anchor Bolts: Section 05501 manufacturer's installation instructions,tanks' <br /> C. Plastic Pipe: Section 16064 shall withstand surface H-20 axle bads <br /> D. Liquid Level Gauges: Section 15174 (32,000 lWaxle). <br /> 2.Internal lAad-. Primary tank shall withstand <br /> 1® Quality Assurance an air pressure test of3-5 psi. Secondary tank <br /> shall be vacuum testedL <br /> A- Acceptable Manufacturer: Modern.Welding WARNVVG Follow manufacturer's testing <br /> Company,Inc, instructions to avoid damage <br /> to the secondary tank. Do not <br /> B. Governing Standards apply positive pressure. <br /> 1. U.L. 58,Underwriters Laboratories, Inc.,steel <br /> Underground Tanks for Flammable and 3.Tanks shall be designed to support accessory <br /> Combustible Liquids. equipment such as ladders,$ubmerged pumps, <br /> 2.U.L. 1746,Underwriters Laboratories,Inc., containment sumps,eft.when installed <br /> Corrosion Protection Systems for Underg'round according to manufacturees instructions and <br /> Storage Tanks. limitations. <br /> 3.NFPA 30 and 30A,National Fire Protection 4.Tanks shall be designed in such a manner to <br /> Assodation Flammable and Combustible Code. provide for monitoring of the interstice. <br /> 4.Uniform Fire Code,International FVe Code 5.Primidry'"shall be designed per Under- <br /> Institute, writers Laboratories,Inc.#58,Table 3.1. <br /> 5.B.O.C.A.,National Fire Prevention Code B. Produce Storage Requirements <br /> 1.Tanks shall be capable of storing liquids with <br /> 1.03 Submittals specific gravity up to 1.1. <br /> A. Shop Drawings; Contractor shall submit 2.Tanks am designed for operation at <br /> copies of shop drawings for each tank. Location atmospheric pressure only. All primary tanks <br /> of fittings and accessories with specific shall be vented. <br /> dimensions shall he shown on all drawings. 3. Tanks shall be capable of storing gasoline, <br /> gasohol,jet fuel,avgas,diesel fuel or methanol <br /> B. Catalog Data: ContractorshaH submit at ambient underground temperature or used. <br /> current copies of manufacturer's literature. for fuel oil at temperatures not to exceed 150 <br /> degrees Fahrenheit. <br /> C. Certification, Each tank shall bear the U.L. 4.The interstice shall be monitored. <br /> listing mark for jacketed underground tank C. Dimensional Requirements <br /> for flammable liquids storage. 1. Nominal capacity of the tank shall be <br /> D. Installation Instructions: Contractor shall gallm& <br /> submit-copies of manufacturer's current 2.Nominal outside diameter of the tank shall be <br /> installation instructions. inches. <br /> 3. OverO length of the tank shall be <br /> app roximaiely-feet, inches. <br />