Laserfiche WebLink
bp <br /> 0 LINE LEAK DETECTOR TEST <br /> Facility#: 2133 Date: 02/24/12 <br /> Address: 2908 Benjamin Holt Dr. <br /> City, State: Stockton CA <br /> Testing Information <br /> 1 2 3 4 5 <br /> Product: 87 91 <br /> Manufacturer Veeder-Root VMI <br /> Leak Detector Serial Number 235252 8071018 <br /> Leak Detector Model No. 848480 LD-2000 <br /> Full Operating Pressure(psi): 30 30 <br /> Test Leak Rate (ml/min)(gph) 3.00 3.00 <br /> Bleed Back Rate (ml): <br /> Turbine Holding Pressure (psi): 0 18 <br /> Metering Pressure (psi): N/A N/A <br /> Open/Trip Time(mechanical only): N/A N/A <br /> Pass/Fail Pass Pass <br /> Comments: <br /> Note: Pass=Leak detector reads leak and meters line. <br /> Fail=Leak detector did not read leak. <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility according to the equipment <br /> manufacturers procedures and limitations and the results as listed are to my knowledge true and correct.The mechanical leak test detector <br /> test pass/fail is determined using a low flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor FASTECH-Fueling&Services Technologies, Inc. <br /> Technician: Isaac Anderson Petro Inc. Lic#: 623541 A-Haz <br /> Signature: <br />