i <br /> i <br /> 1 <br /> i <br /> 1 <br /> INSTALLATION CHECKLi <br /> Xerxes Century-Cast Fiberglass Underground Storage Tank(s) <br /> 1 <br /> To: Installation Supervisor From: Xerxes Corporation Subj.: Installation Checklist <br /> 1 <br /> i Read the preceding Tank Installation Instructions, then fill in the information below. As the tank installation progresses,fill in each applicable <br /> inspection,testing and installation checklist item below,initialing the item as its conditions are satisfactorily met.(Refer to Installation Instructions <br /> 1 for details.) <br /> When the checklist is complete,tear off at the dotted line and mail to: <br /> i XERXES CORPORATION,7901 Xerxes Avenue South,Minneapolis,MN 55431. <br /> 1 <br /> INSTALLATION DATE(S) <br /> SITE OWNER <br /> i SITE ADDRESS <br /> city State State Tip <br /> Street <br /> 1 INSTALLATION CONTRACTOR <br /> 1 <br /> INSTALLATION SUPERVISOR <br /> 1 <br /> PRIOR TO INSTALLATION: Verified by: <br /> A.Visual inspection.No evidence(holes,cracks,deep scrapes)in domes,ribs or flats of damage to the tank from physical <br /> 1 abuse or a blow from a hard object. <br /> i B.Physical testing.Completed in accordance with current Xerxes Installation Instructions(5 psig pressurization and soap <br /> i test). <br /> C.Backfill material(indicate material type). <br /> 1.Pea Gravel per specification in Installation Instructions. <br /> i 2.Crushed Gravel or Stone per specification in Installation Instructions. <br /> 3.Other(requires specific approval by Xerxes rep.)Describe: <br /> D.Excavation hole size.Hole dimensions are correct per Installation Instructions for stable and unstable walls. <br /> 1 E.Hole conditions(select one): <br /> 1.Dry hole.Ground water elevation not anticipated to reach tank and area not subject to flooding.(Dry hole installation) <br /> 1 2.Wet hole.Ground water elevation expected to reach tank or area subject to flooding.(Wet hole installation) <br /> F Traffic load(select one): <br /> 1.Traffic loading anticipated.(Requires deep burial per Installation Instructions.) <br /> 2.No traffic loading(Allows normal burial per Installation Instructions.) <br /> DURING INSTALLATION: Verified by: <br /> A.Backfill material bed is level and at 12"(300mm)minimum depth over native soil or slab prior to setting tanks in place. <br /> B.Tanks set in place with correct spacing from wall and other tanks. <br /> C.Deadmen and tie downs positioned and secured in accordance with Installation Instructions.(Wet hole installation) <br /> D.Backfill material tamped and compacted to fill all voids around tank.-- <br /> E.Tank properly ballasted during backfill.(Wet hole installation only) <br /> F Tank(s)buried at proper depth to conform to wet or dry hole;traffic or no traffic conditions. <br /> 1 <br /> 1 <br /> INSTALLATION TESTING: <br /> i A.All tanks with manways must be inspected from the inside after installation. <br /> 1.Check for backfill voids(especially around the bottom 1/3 of tank)after the first 24"(600mm)of backfill are in place by <br /> gently tapping a blunt wooden object against the tank wall and listening for hollow sounding areas. <br /> 2.Visually inspect the tank for any signs(cracks,holes,indentations)of physical damage. <br /> MEASUREMENT OF DEFLECTIONS: <br /> A.All tanks must be measured to determine vertical tank deflection during installation.On manway tanks,measurements <br /> 1 <br /> are to be made inside the tank as close to the center as possible.On non-manway tanks,use the procedure described <br /> 1 below <br /> interior diameter of tank interior diameter of tank <br /> 1 prior to backfilling. after backfilling to subgrade. Deflection <br /> t (A) _ (B) _ <br /> r Maximum Allowable Deflections: Tank Diameter Deflection <br /> 4' <br /> t 4 <br /> i6' 5/e" <br /> I 8' 11/4" <br /> r 10' 1 Yz" <br /> Vertical deflection in excess of these values indicates improper installation and voids the tank warranty. <br /> B.NOWMANWAY TANK MEASURING TECHNIQUE: <br /> 1 1.Using a gauge stick,measure from the tank bottom to the bottom of the fitting before backfilling.Enter the result in <br /> _ (A)above. <br /> 2.After backfilling to subgrade,use the same gauge stick with a nail driven into it at the 1"mark,catch the nail under <br /> 1 the bottom of the tank fitting and measure to the top of the fill tube(subtract 1"to allow for the distance of the nail <br /> from the end of the gauge stick). Now measure the distance from the bottom of the tank to the top of the fill tube. <br /> Subtract the fill tube length measurement from the total measurement and enter the result in(B)above. <br /> e <br /> 1 <br /> i <br /> t <br /> _ 1 <br /> CX 123!785 <br /> 1 <br /> 1 <br /> 1 <br /> t <br /> 1 <br /> 1 <br /> 1 <br /> 1 <br /> t <br /> t <br /> 1 <br />