Triangle Environmental, Inc. <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Facility # 2705448 <br /> Tank #: 1 Test Date: 3/15/03 <br /> Product: Unleaded Premium Work#: 302774 <br /> Test Method: System 5000 Test Method: R.J.FTA <br /> Capacity: 10369 Manufacturer: Red Jacket <br /> Diameter(in): 110 L/D Model: <br /> Product Level(in): 75.9 L/D Serial#: <br /> Liquid Volume(Gals): 7227 Line Drain Back(ml): <br /> Liquid Percent(%): 69.7% L/D Trip Time(sec): <br /> Specific Gravity: 0.760 Holding Pressure(psi): <br /> Coef,of Expansion: 0.000654 Metering Pressure(psi): <br /> Water On Tank(in): 0 L/D Test Rate(gph): <br /> Water In Tank(in): 0 L/D Result: N/A <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): 2.1 <br /> Test Start Time: 12:50:00 PM <br /> Test End Time: 12:55:00 PM Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: PASS System Type: Pressure <br /> Line Pressure(psi): 55 <br /> Line Start Time: 5:00:00 PM <br /> Test Method: ULLAGE Line End Time: 5:15:00 PM <br /> UllageVolume(gals.): 3142 Line Start Level: 100 <br /> Ullage Test Time: 12:50:00 PM Line End Level: 93 <br /> Ullage Vacuum(psi): 2.8 Line Test Rate(gph): -0.007 <br /> Ullage Result: PASS Line Test Result: PASS <br /> 2 <br />