Laserfiche WebLink
y <br /> Triangle Environmental, Inc. <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Circle K Stores # 05448 <br /> Tank #. 3 Test Date: 11/13/02 <br /> Product: Unleaded Premium Work#: 302611 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: 10007 Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: 02061362 <br /> Liquid Volume(Gals): Line Drain Back(ml): 120 <br /> Liquid Percent(%): L/D Trip Time(sec): 3 <br /> Specific Gravity: Holding Pressure(psi): 29 <br /> Coef.of Expansion: Metering Pressure(psi): 22 <br /> Water On Tank(in): L/D Test Rate(gph): 1.7 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> i <br /> Test Start Time: j <br /> Test End Time: Test Method: <br /> Test Rate(gph): Pump Brand: FE Petro <br /> Test Result: N/A i System Type: Pressure <br /> L Line Pressure(psi): <br /> Line Start Time: <br /> Test Method: ULLAGE i Line End Time: <br /> U11ageVolume(gals.): <br /> Line Start Level: <br /> Ullage Test Time: l Line End Level: <br /> Ullage Vacuum(psi): Line Test Rate(gph): <br /> Ullage Result: N/A Line Test Result: N/A <br /> 001 OEM <br /> 4 <br />