Laserfiche WebLink
Triangle Environmental, Inc. <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Circle K Stores # 05448 <br /> Tank #s 2 Test Date: V/ 7/02 <br /> Product: Unleaded Regular Work#: 7405944 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: 10007 Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: 02061360 <br /> Liquid Volume(Gals): Line Drain Back(ml): 125 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 30 <br /> Coef.of Expansion: Metering Pressure(psi): 18 <br /> Water On Tank(in): L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? Yes <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: N/A System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 10:16:00 AM <br /> Test Method: ULLAGE Line End Time: 10:31:00 AM <br /> U11ageVolume(gals.): <br /> Line Start Level: 280 <br /> Ullage Test Time: Line End Level: 290 <br /> Ullage Vacuum(psi): Line Test Rate(gph): 0.011 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 2 <br /> J <br />