Triangle Environmental Inc <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Tosco Facility# 05448 <br /> Tank #: 2 Test Date: 10/19/2001 <br /> Product: Unleaded Regular Work#: 7405574 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: 10007 Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> i <br /> Product Level(in): L/D Serial#: 95581 <br /> Liquid Volume(Gals): Line Drain Back(ml): 150 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 40 <br /> Coef.of Expansion: Metering Pressure(psi): 22 <br /> I Water On Tank(in): L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> '. <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph ` Pump Brand: FE Petro <br /> Test Res?lt: N/A System Type: Pressure <br /> Line Pressure(psi): 50 <br /> I Line Start Time: 11:35:00 AM <br /> Test Method: ULLAGE Line End Time: 11:50:00 AM <br /> i <br /> UllageVolume(gals.): Line Start Level: 255 <br /> Ullage Test Time: Line End Level: 260 <br /> Ullage Vacuum(psi): Line Test Rate(gph): 0.005 <br /> Ullage Result: N/A <br /> Line Test Result: PASS <br /> 2 <br />