Laserfiche WebLink
Triangle Environmental Inc <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Tosco Facility # 05448 <br /> Tank #: 3 Test Date: 10/19/2001 <br /> Product: Unleaded Premium Work#: 7405574 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: 10007 Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: 05581 <br /> Liquid Volume(Gals): Line Drain Back(ml): 150 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 30 <br /> Coef.of Expansion: Metering Pressure(psi): 22 <br /> Water On Tank(in): L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph Pump Brand: FE Petro <br /> Test Res?lt: N/A System Type: Pressure <br /> Line Pressure(psi): 50 <br /> IBMLine Start Time: 11:01:00 AM <br /> Line End Time: 11:16:00 AM <br /> Test Method: ULLAGE <br /> UllageVolume(gals.): Line Start Level: 210 <br /> Ullage Test Time: Line End Level: 205 <br /> Ullage Vacuum(psi): Line Test Rate(gph): 0.000 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 4 <br />