Laserfiche WebLink
LG 113 Vendor/Template Page 1 of 2 <br /> Local Guidance (LG) Letter 113 <br /> [updated:February 23,2006 <br /> Issue Date:November 22,1995 <br /> Revision Date:March 28,2002 <br /> Veeder-Root <br /> ILS-250, ILS-350,TLS-2501,250i Plus,300,300C,3001,30013C, TLS-350 Series, Red Jacket ProMax and P <br /> Interstitial Liquid Sensor for Fiberglass Tanks 0794390-401, 404, 407, 409, Interstitial Liquid Sensor for <br /> 0794390-420,460, Liquid Sensor for Sumps 794390-206 <br /> INTERSTITIAL DETECTOR (LIQUID-PHASE) <br /> Detector: <br /> Output type: qualitative <br /> Sampling frequency: continuous <br /> Operating principle: float switch <br /> Test Results: <br /> .unleaded gasoline* synthetic gasoline** <br /> Interstitial Liquid Sensor for Fiberglass <br /> Tanks 0794390-401, 404,407,409 <br /> Response time (min) 3.66 3.45 <br /> Recovery time (min) <1 <1 <br /> Product activation height(cm) 1.28 1.27 <br /> Lower detection limit(cm) 1.84 1.65 <br /> Interstitial Liquid Sensor for Steel Tanks <br /> 0794390-420,460 <br /> Response time (min) 6.00 6.51 <br /> Recovery time (min) <1 <1 <br /> Product activation height(cm) 3.67 3.62 <br /> Lower detection limit(cm) 4.05 4.17 <br /> Liquid Sensor for Sumps 0794390-206 <br /> Response time(min) 8.19 8.49 <br /> Recovery time (min) <1 <1 <br /> Product activation height(cm) 4.12 3.95 <br /> Lower detection limit(cm) 4.67 4.36 <br /> httn-//www.-zwrr.h.rs anv/nwnhome/iict/leak nrevention/10 I3/Vendnr Filet/veeder root. m.... 3/22/06 <br />