T 3:DIESEL <br />PRODUCT CODE 3 <br />THERMAL COEFF :.000450 <br />TANK DIAMETER 117.50 <br />TANK PROFILE 4 PTS <br />FULL VOL 10369 <br />86.1 INCH VOL 8497 <br />58.8 INCH VOL 5244 <br />29.4 INCH VOL 1945 <br />METER DATA YES <br />END FACTOR: HEMISPHER <br />CAL UPDATE: IMMEDIATE <br />FLOAT SIZE: 4.0 IN. <br />WATER WARNING 1.0 <br />HIGH WATER LIMIT: 1.5 <br />WATER ALARM FILTER: LOW <br />MAX OR LABEL VOL: 10369 <br />OVERFILL LIMIT 90% <br />9332 <br />HIGH PRODUCT 95% <br />9850 <br />DELIVERY LIMIT 8% <br />829 <br />LOW PRODUCT 360 <br />LEAK ALARM LIMIT: 99 <br />SUDDEN LOSS LIMIT: 99 <br />TANK TILT 5.75 <br />PROBE OFFSET 0.00 <br />SIPHON MANIFOLDED TANKS <br />TO: NONE <br />LINE MANIFOLDED TANKS <br />TO: NONE <br />LEAK MIN PERIODIC: 00/0 <br />0 <br />LEAK MIN ANNUAL 01/0 <br />0 <br />PERIODIC TEST TYPE <br />STANDARD <br />ANNUAL TEST FAIL <br />ALARM DISABLED <br />PERIODIC TEST FAIL <br />ALARM DISABLED <br />GROSS TEST FAIL <br />ALARM DISABLED <br />ANN TEST AVERAGING: OFF <br />PER TEST AVERAGING: OFF <br />TANK TEST NOTIFY: OFF <br />TNK TST SIPHON BREAKOFF <br />DELIVERY DELAY 2 MIN <br />PUMP THRESHOLD : 10.00% <br />L11 :DISP 3-4 <br />LEAK TEST METHOD ';TRI-STATE (SINGLE FLOAT) <br />- - - - - - - - - - - - CATEGORY DISPENSER PAN <br />TEST ON DATE : AL ) r <br />JAN 29. 2009. <br />START TIME : D I SABLE$ il'L: L 12 : p I SP 5-6 <br />TEST RATE :0.20 SHR TRI-STATE (SINGLE FLOAT) <br />DURATION 2 HOURS CATEGORY : DISPENSER PAN <br />TST EARLY STOP:DISABLED <br />LEAK TEST REPORT FORMAT L13:DISP 7-8 <br />NORMAL TRI-STATE (SINGLE FLOAT) <br />CATEGORY : DISPENSER PAN <br />LIQUID SENSOR SETUP <br />L 1:87 STP <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : STP SUMP <br />L 2:91 STP <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : STP SUMP <br />L 3:DIESEL STP <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : STP SUMP <br />L 4:87 ANNULAR <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : ANNULAR SPACE <br />L 5:91 ANNULAR <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : ANNULAR SPACE <br />L 6:DIESEL ANNULAR <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : ANNULAR SPACE <br />L 7:87FILL SUMP <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : PIPING SUMP <br />L 8:91FILL SUMP <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : PIPING SUMP <br />L 9:DIESELFILL SUMP <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : PIPING SUMP <br />L10:DISP 1-2 <br />TRI-STATE (SINGLE FLOAT) <br />CATEGORY : DISPENSER PAN <br />OUTPUT RELAY SETUP <br />R 1:87 STP <br />TYPE: <br />STANDARD <br />NORMALLY CLOSED <br />TANK #: I <br />IN -TANK ALARMS <br />T I:HIGH WATER ALARM <br />T 1:LOW PRODUCT ALARM <br />LIQUID SENSOR ALMS <br />ALL:FUEL ALARM <br />ALL:SENSOR OUT ALARM <br />ALL:SHORT ALARM <br />ISD SITE ALARMS <br />ISD GROSS PRES FAIL <br />ISD DEGRD PRES FAIL <br />ISA VAPOR LEAK FAIL <br />ISD SETUP FAIL <br />ISD SENSOR OUT FAIL <br />ISD HOSE ALARMS <br />ALL:GROSS COLLECT FAIL <br />ALL:DEGRD COLLECT FAIL <br />ALL:FLOW COLLECT FAIL <br />R 2:91 STP <br />TYPE: <br />STANDARD <br />NORMALLY CLOSED <br />TANK #: 2 <br />IN -TANK ALARMS <br />T 2:LOW PRODUCT ALARM <br />LIQUID SENSOR ALMS <br />ALL:FUEL ALARM <br />ALL:SENSOR OUT ALARM <br />ALL:SHORT ALARM <br />ISD SITE ALARMS <br />ISA GROSS PRES FAIL <br />ISD DEGRD PRES FAIL <br />ISD VAPOR LEAK FAIL <br />ISD SETUP FAIL <br />ISD SENSOR OUT FAIL <br />