Page 1 of 1 <br />SPILLIOVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Fill Riser Containment Sumps <br />Fill Riser Containment Sumps are Present, but were Not Tested <br />Test Method Developed By: r Spill Bucket Manufacturer f+ Industry Standard C Professional Engineer <br />Other (Specify): <br />Test Method Used By: r Pressure r Vacuum 1. Hydrostatic <br />Other (Specify): <br />Test Equipment Used: EVACUUM TEST Equipment Resolution: <br />Bucket Diameter. 14.00 14.00 14.00 <br />Bucket Depth: 14.50 16.50 14.00 <br />Wait time between pressure/vacuum/water amend starting test 0 min 5 min 0 min m i n <br />Test Start Time: <br />09:09:00 <br />09:27:00 <br />09:22:00 <br />Initial Reading (R): <br />30.00 in. H2O <br />16.50 in. H2O <br />30.00 in. H2O <br />Test End Time: <br />09:10:00 <br />10:27:00 <br />09:23:00 <br />Final ReadingrRd: <br />27.00 in. H2O <br />16.50 in. H2O <br />30.00 in. H2O <br />Test Duration: <br />1 min <br />1 hr <br />1 m i n <br />Change in ReadingrR.R�: 1 -3.00 in. H2O 1 0.00 in. H2O 1 0.00 in. H2O <br />Pass/Fail Threshold or Criteria: 1 +/-4.00 <br />+/-0.00 <br />+1-4.00 <br />Comments ? (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />WO: 2309117 <br />