Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br />Tanknology <br />TEST DATE: 07/19/99 K, BUILDING 200 WORK ORDER NUMBER2209388 <br />CLIENT:WENDT CONSTRUCTION AUSTIN, TEXAS 78757 (512) 451-6334 SITE:CHEVRON STATION 93232 <br />Tank ID: 87 1 <br />Tank manifolded: No <br />Bottom to top fill in inches: <br />141.0 <br />Product: REG UNLEAD <br />Vent manifolded: No <br />Bottom to grade in inches: <br />147.0 <br />Capacity in gallons: 9,684 <br />Vapor recovery manifolded: YES <br />Fill pipe length in inches: <br />51.0 <br />Diameter in inches: 90.00 <br />Overfill protection: YES <br />Fill pipe diameter in inches: <br />4.0 <br />Length in inches: 356 <br />Overspill protection: YES <br />Stage I vapor recovery: <br />DUAL <br />Material: DW FISERG <br />Installed: ATG <br />Stage II vapor recovery: <br />BALANCE <br />CP installed on: <br />COMMENTS <br />E <br />Start (in) <br />End (in) <br />Dipped Water Level: 0.00 <br />0.00 <br />New/passed Failed/replaced New/passed <br />Failed/replaced <br />Dipped Product Level: 59.75 <br />59.75 <br />L.D. #1 L.D. #1 L.D. #2 <br />L.D. #2 <br />Probe Water Level: 0.003 <br />0.006 <br />Make: <br />Ingress Detected: Water N Bubble <br />N UllageN <br />Model: <br />Test time: 11:25-13:41 <br />S/N: <br />Open time in sec: <br />Inclinometer reading: <br />0.00 <br />Holding psi: <br />VacuTect Test Type: multiple tanks <br />Resiliency cc: <br />NOT NOT <br />VacuTect Probe Entry Point: Fill <br />Test leak rate ml/m: <br />TESTED TESTED <br />Pressure Set Point: <br />-0.50 <br />Metering psi: <br />Tank water level in inches: <br />0.00 <br />Calib. leak in gph: <br />Water table depth in inches: <br />145.00 <br />Results: <br />Determined by (method): <br />SURVEY <br />Result: <br />PASS <br />COMMENTS <br />COMMENTS <br />Material: DW FISERG <br />Diameter (in): <br />2.0 <br />Length (ft): <br />100.0 <br />Test psi: <br />50 <br />Bleedback cc: <br />75 <br />Test time (min): <br />30 NOT <br />NOT NOT <br />Start time: <br />10:00 TESTED <br />TESTED TESTED <br />End time: <br />10:30 <br />Final gph: <br />0.009 <br />Result: <br />PASS <br />Pump type: <br />PRESSURE <br />Pump make: <br />FE PETRO <br />COMMENTS <br />Impact Valves Operational: YES <br />Printed 07/23/1999 09:19 <br />