Laserfiche WebLink
SWRCB.January 2002 Page of <br /> 7, UNDER-DISPENSER CONTAINMENT(UDC}TE T_L IG <br /> I est Method Developed By: UDC Manufacturer L'Industry Standard X Professional Engineer <br /> 1 Other(Specify) <br /> Test Method Used: i Pressure Vacuum X Hydrostatic <br /> U Other(Specify) <br /> _._ Eqrupment Resolution <br /> Test Equipment Used Caldwell Systems <br /> 005/'30 min <br /> .m • : <br /> R. <br /> C Manufacturer: UDC t€ t-2 UDC#3-4 _ UDC#5-6 UDC#7-8 � <br /> UD er: "Total Containmen! Total Containment Total Containment "notal Containment <br /> UDC Material: Fiberglass Fiberglass Fiberglass j Fiberglass <br /> UDC Depth: 28"__� 28' _ 28" 28" <br /> Haight from UDC Bottom to Top 8" 8" 9" _ 9" <br /> of Hrolzest Piping Penetration: <br /> I leight from UDC Bottom to 7" 7" 7' I T <br /> Lowest Electrical Penetration: <br /> _ _. ............ <br /> Condition of UDC prior to Dry Dry Dry Dry <br /> testing: <br /> 1. Portion of IJDC Testcd� 2'"above Highest Piping Penetration <br /> Does turbine shut down when j <br /> UDC sensor detects liquid (both x Yes No 1_1 NA x Yes No t_I NA x Yes . No NA x Yes No NA <br /> ---------------- <br /> R product and water)?' <br /> I urbine shutdown response time <br /> Is system programmed for fal- <br /> t� Sate shutdown`�� x Yes No I.I NA x Yes No �=NA x Yes No ❑NA NN <br /> j x Yes o A <br /> j , <br /> Was fail-sate verified to be -,yes x No NA ❑Yes x No NA FJ Yes x No NA L'Yes x No NA <br /> 9 <br /> a[? <br /> operation <br /> ........ . __._. ..... .... -- <br /> Wart time between applying <br /> }pressure/vacuum/water and 5 min 5 min 5 min 5 min 3 <br /> startinp,test <br /> _.. .........__..- <br /> fcst Start Time: 1 f:45 11:5 1 i:55 12:05 <br /> ....... —. ..._ . . _._. . —__._._.�. __.._._ _ <br /> initial Readinr(Ri)� 00' 00" 00" 00 <br /> _ _ <br /> est Ind 1 nne: �_ 12:l5 12:20 12:25 12-35 <br /> _ _. <br /> Final Reading(RF) 00 .00 .00 .00 _ <br /> 1 est Duration: 30 min 30 min 30 min 30 min <br /> Change in Reading(RF-Ri) 00 .00 .00 j 00 <br /> �.�_ _ <br /> Pass/_Fail I hreshold or Criteria: 005/30 rain 005130 min 005/30 min .005/30 <br /> min <br /> fest Result: � x ]Pass D Fail x Pass 1:1 Fail x Pass fI Fail x Pass I Fail <br /> _.._.__.. _—..... ....... _ ..... ...._. —._._.. _._ <br /> Was sensor removed for testing? x Yes No �:I NA } xYes I i No `:`1NA x Yes C+No CRNA x Yes - No NA <br /> - — - _. .._ <br /> Was sensor properly replaced and x Yes No NA i x Yes Na NA x Yes l:No 3.:: NA x Yes ; =No NA <br /> crified funcrional after testing`? <br /> Ctirltti eat; —(include inlorrrration on repairs atude prior to testing, and recommended follow-itp Jbr failed testa) <br /> If the entire depth of the UDC is not tested,specify how much was tested. If the answer to an of the questions indicated with an <br /> asterisk(*) is"NO"or"NA", the entire UDC must be tested. (See SWR.CB LG-160) <br />