Laserfiche WebLink
• I <br /> RECEIVED <br /> SWRCB,January 2002 p4QV I Qf2015 <br /> 4. TANK ANNULAR TESTING ENVIRONMENTALLLMAiXLM <br /> AIT <br /> Test Method Developed By: X Tank Manufacturer Industry Standard Professional Engineer <br /> Other(Specify) <br /> Test Method Used: Pressure X Vacuum Hydrostatic <br /> Other(Spec) <br /> Test Equipment Used: Gast Vacuum Pump/Vacuum Gauges in Hg. Equipment Resolution: - '/2"x-30"Hg. <br /> Tank#1 Tank#2 Tank#3 Tank# <br /> Is Tank Exempt From Testing?' No No No <br /> Tank Capacity: l OK l OK l OK <br /> Tank Material: Fiberglass Fiberglass Fiberglass <br /> Tank Manufacturer: XERXES XERXES XERXES <br /> Product Stored: Supreme 91 Plus 89 Regular 87 <br /> Wait time between applying 15 Minutes 15 Minutes 15 Minutes <br /> vacuum and starting test: <br /> Test Start Time: 10:10 10:20 10:30 <br /> Initial Reading(Rj): -10 Hg. -10 Hg. -10 Hg. <br /> Test End Time: 11:10 11:20 11:30 <br /> Final Reading(RF): -10 Hg. -10 Hg. -10 Hg. <br /> Test Duration: I Hour I Hour 1 Hour <br /> Change in Reading(RF-R,): 0"Hg. 0"Hg. 0"Hg. <br /> Pass/Fail Threshold or Criteria: ➢ -2 Hg. ➢ -2 Hg. ➢ -2 Hg. ➢ <br /> Test Result: Pass Pass Pass <br /> Was sensor removed for testing? No No No <br /> Was sensor properly replaced and N/A N/A N/A <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23, Section 2637(a)(6)) <br />