Laserfiche WebLink
02/01/1994 10:50 707374266 NDE ENVIRONMENTAL PAGE 09 <br />1 <br />INDIVIDUAL TANKAINE/LEAK DETECTOR TIGHTNESS TEST REPORT <br />Test date: January 29, 1994 Work order number: <br />Client: UNOCAL OIL CORP X2186 <br />Site: #5W <br />Test type: VPLT <br />TANK INFORMATION <br />TANK TEST RESULTS <br />Tank: 1 Product: UNLEADED <br />Capacity: 11,627 (gal) <br />Fuel level at start: 57.50 (in) <br />Fuel volume at start: 7 <br />Diameter: 92-00" Length: 409" <br />Material: FIBERGLASS <br />645 <br />Water level at start: 6.00{in) <br />Manifolded? Tank: No <br />Vent= <br />Test time: 18:45-20:47 <br />Specific gravity 0.743 <br />Water <br />V/R: YFS <br />table depth: 87.00 (in) <br />Determined by (method): Well <br />Bottom to top fill: 132.0 in <br />Bottom to grade: 136.0 in <br />Volume change: 0.001 (gph) <br />Fill pipe lengthe 41.0 in <br />lini <br />RESULT: PASS <br />Fill pipe diameters 4.0 <br />LINE INFORMATION RESULTS <br />ULLAGE TEST RESULTS <br />Pump type: PRESSURE Make: RED JACKET Test time: <br />Line A Line B Line <br />Line materl FIBERGL <br />ITst <br />C Line D Ullage volume: <br />Diameter(inj 2.0 <br />3,982 (gal) <br />Ullage pressure: <br />prs psi 50 0 <br />Vol chgfgph 0.016 0.000 <br />0 0 2.45 (psi) <br />0_ 0. RESULT: <br />RESULT PASS <br />PASS <br />LEAK DETECTOR INFOAPATION <br />FAILED/REPLACED LEAK DETECTOR <br />Make: RED JACKET del: X.L.D. <br />Make: RED JACKET Model:D.L.D. <br />S/:2023916 RESULT: PASS <br />S/: RESULT: FAIL <br />Calibrated leak (gph): 3.00 <br />Calibrated leak (gph): 3.00 <br />f <br />R=95% 7073742663 02-01-94 09:53AM P009 #16 <br />1 1 <br />