s <br />CAPACITY 12000 g PRECISION UNDERGROUND TANK TESTING RESULTS Patent Pending <br />TANK <br /># Super unleaded <br />PAGE 2 <br />STAT <br /># 5886 GENERAL REPORT FORM <br />TEST <br />DATE: 02/27/90 Copyright 1985 <br />NDE TECHNOLOGY, <br />INC. PROPRIETARY <br />1. <br />Capacity of the tank <br />12,000 Gallons <br />2. <br />Present or past contents <br />Super Unleaded <br />3. <br />Tank construction material <br />Fiberglass <br />4. <br />Tank end deflection <br />0" <br />5. <br />Internal diameter of tank <br />92" <br />6. <br />Fill pipe internal diameter <br />4" <br />7. <br />Fill pipe length <br />47" <br />8. <br />Air vents <br />1. <br />9. <br />Type of fill pipe cap <br />Cam. <br />10. <br />Type of pumps associated <br />with the appurtenant piping <br />R.J. Turbine <br />11. <br />Coefficient of thermal <br />expansion .0006363 <br />volumetric coeffic:ient <br />of expansion/deg <br />12. <br />Specific gravity <br />.751 <br />13. <br />Hulk modulus <br />188,000 <br />14. <br />Type of phase II vapor <br />recovery system <br />Balanced <br />15. <br />Depth of groundwater from <br />grade level <br />BELOW BOTTOM OF' TANK <br />16. <br />Date and Time storage <br />tank system was <br />02/27/90 <br />filled for testing <br />16:00 <br />17. <br />Testing fluid <br />Super Unleaded <br />�18. <br />NOTES: <br />Technician could not <br />remove the drop <br />tube. Tested with drop <br />tube in place. <br />NDE TECHNOLOGY, INC. PROPRIETARY <br />WATT INC. 3131 FAIRHAVEN DRIVE, BAKERSFIELD, CA 93308 (805) 322-9827 <br />