Laserfiche WebLink
0 <br /> Triangle Environmental, Inc. <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 <br /> (818)840-7020 (818)840-6929 <br /> UST TESTING SYSTEMS SUMMARYSHEET <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Phillips 66 company Phillips Facility # 31010 <br /> 1500 North Priest Drive <br /> Tempe, AZ 85281 Test Date: /�7 <br /> / 2/02 <br /> Kathy StrickLand <br /> (602)728-7149 <br /> Facility: 255886 Work#: 7405901 <br /> Phillips Facility# 31010 County: SAN JOAQUIN <br /> 2701 W MARCH LN Cross Street: I-5/MARCH LN <br /> STOCKTON, CA 952070000 <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rate/Results Ullage Result Rate/Result L/D Result <br /> 1 Unleaded Regular N/A N/A 0.005 PASS PASS <br /> 2 Unleaded Premium N/A N/A 0.005 PASS PASS <br /> 3 Diesel N/A N/A 0.011 PASS PASS <br /> Certified By: Technician: Steve Sweatt State Lic.#s: CA-1616 <br /> ?197 Mfgr's#: TEI-056 <br /> Comments: <br /> Compliance L/D,PL,&monitor certification,Grd. <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95% and Pfa<5%as required by Local,State and Federal EPA UST Technical <br /> Standards Part 280 for precision testing systems. This SB-989 secondary containment testing system <br /> exceeds the criteria for detection as required by state and local agencies. <br />