Laserfiche WebLink
Triangle Environmental, c. <br /> SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Phillips Facility <br /> Tank ##e 3 Test ate: 7/ 2/02 <br /> Product: Diesel Work#: 7405901 <br /> ON= mmmu� <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: 47531 <br /> Liquid Volume(Gals): Line Drain Back(ml): 95 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 32 <br /> Coef.of Expansion: Metering Pressure(psi): 10 <br /> Water On Tank(in): L/D Test Rate(gph): 3.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): New leak detector? No <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Pump Brand: Red Jacket <br /> Test Rate(gph): <br /> Test Result: NIA System Type: Pressure <br /> Line Pressure(psi): 50 <br /> 1. - <br /> ')C Line Start Time: 12:21:00 PM <br /> Test Method: ULLAGE Line End Time: 12:36:00 PM <br /> UllageVolume(gals.): Line Start Level: 260 <br /> i <br /> Ullage Test Time: Line End Level: 270 <br /> Ullage Vacuum(psi): Line Test Rate(gph): 0.011 <br /> Ullage Result: N/A Line Test Result: PASS <br /> Effi <br /> Nil 1� <br /> .. .. ........ rr <br /> 4 <br />