Laserfiche WebLink
v <br /> PEI- <br /> STOCKTON <br /> SERVICE STATION EQUIPMENT CO. <br /> 808 N. UNION STREET19 <br /> STOCKTON, CA 95205-4152 <br /> PHONE 209.464.8333 FAX 209.464.8349 <br /> LDT-890 LEAK DETECTOR TEST RECORD <br /> CUSTOMER: Pacific Mini Mart&Gas DATE: August 24,2005 <br /> LOCATION: 4511 Pacific Avenue <br /> CITY: Stockton STATE: CA ZIP: 95207 <br /> TECHNICIAN: RANDY CHADWICK <br /> Submersible Pump Identification <br /> Manufacturer Model Serial Number <br /> Red Jacket 3/4 H.P. 4" 04083065 <br /> Leak Detector.Identification <br /> Manufacturer Description Other Style Leak Detector <br /> Vaporless <br /> Diaphragm-type <br /> Piston-type X <br /> Leak Detector in Submersible Pump <br /> Test at Dispenser <br /> 1. Operating Pump Pressure 26 psi (Purging Test System) <br /> 2. Gallons per hour rate 3 GALLONS (Leak Test,Phase I) <br /> 3. Line pressure with pump shut off 12 psi (Leak Test Phase I) <br /> 4. Bleed-Back Test with pump off 125 ml (Bleed-back Test) <br /> 5. Step-through time to full flow 5 seconds (Step-through Time) <br /> 6. Leak detector stays in leak search position. (Leak Test Phase II)Yes X No <br /> LEAK DETECTOR TEST <br /> Note: Pass=Leak detector fits test protocol <br /> Fall =Leak detector fails test protocol <br /> Pass X <br /> Fail <br /> Form 890C <br />