Laserfiche WebLink
INVOICE #JB000035 TEST DATE: 11 /20/96 <br /> AFFORDA—TEST <br /> POR 36 THORNTON, CA. 95686 <br /> ( 209)794-01.02 FAX ( 209794-01.12 <br /> TANK STATUS EVALUATTON REPORT <br /> ----------------------------- <br /> ***** CUSTOMER DATA ***** ***** SITE DATA ***** <br /> FLAME LIQUORS-- EXXON FLAME LIQUORS-- EXXON C5 <br /> 1301 WEST KETTLEMAN LANE 1301 WEST KETTLEMAN LANE �' <br /> @ HAM LANE @ HAM LANE <br /> LODI, CA LODT, CA <br /> 95240 95240 ^ca <br /> CONTACT: GRAFFIGNA, PETE CONTACT: GRAFFTGNA, PETE W -s <br /> PHONE #: (209)334-3233 PHONE # : ( 209)334-3233 <br /> ***** COMMENT LTNES ***** <br /> THREE 10K TANKS, PRESSURE T,TNES, BALANCED VR SYSTEMS. <br /> CURRENT EPA STANDARDS DTCTATE <br /> THAT FOR UNDERGROUND FUEL TANKS, THE MAXIMUM ALLOWABLE LEAK/GAT_N RATE <br /> OVER THE PERTOD OF ONE HOUR TS . 05 GALLONS. <br /> TANK #1. : SUPER UNLEADED TYPE: STEEL RATE: .030620 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: —. 1.8 <br /> TANK IS TIGHT. <br /> TANK #2: REG UNLEADED TYPE: STEET, RATE: .005421 G.P.H. LOSS <br /> ULLAGE: PASS SIGNAL/NOISE: .02 <br /> TANK TS TIGHT. <br /> TANK #3: PLUS UNLEADED, TYPE: STEET., RATE: .002500 G.P.H. GAIN <br /> ULLAGE: PASS SIGNAL/NOISE: —.07 <br /> TANK IS TIGHT. <br /> EQUIPMENT: USTEST <br /> OTTL# 97-1143 <br /> OPERATOR: LYLE D. NIMMO SIGNATURE: Ajt� <br /> 7ANE A. NIMMO, Trainee f ? ,, <br />