CONTAINMENT:
<br /> Sump RiserS_y
<br /> j Rings-___
<br /> Monitor Well
<br /> With 2"Fittings
<br /> Annular Space
<br /> L
<br /> 500 1,000 6-5 3/8" 51" 46" 4,000 3/16"
<br /> 675 1,087 4'-5 3/8" 10" 65" 5,500 3/16'
<br /> 1,000 1,404 6'-5 3/8' 70" 65" 8.000 3/16°
<br /> 2,000 2,319 12'-4 5/8" 70" 65" 15,500 3/16'
<br /> 2,500 2,777 15'-4 5/8" 70' 65" 19,500 3/16"
<br /> 3,000 3,233 18'-4 5/8" 70" 65" 23,000 3/16"
<br /> 3,000 3,706 8'-8 1/2' 102" 97" 10,700 3/16"
<br /> i
<br /> 4,000 4,147 24'-41/2" 10" 65" 29,500 114'
<br /> 4.000 4,397 11'-11/4" 102" 91" 30,5(10 3/16'
<br /> 5,000 5,186 13'-9 3/8" 102" 97" 38,500 1/4'
<br /> 6,000 6,171 17'-13/8" 102" 97" 48,500 1/4"
<br /> 8,000 7,745 22'-4 5/8" 102" 91" - 63,500 1/4"
<br /> 10,000 8.102 15'-101/2- 134 3/8" 129 3/8" 78,000 1/4'
<br /> 10.000 9.124 21'-0 5/8' 102' 97" 77,000 1/4-
<br /> 12,000 9,306 18'-11 1/2" 1343/8- 129 3/8" 93,900 1/4"
<br /> 12,000 10,698 32'-3 7/8" 102" 97" 92,500 1/4"
<br /> 15,000 14,177 23'-7 7/8" 134 3/8" 129 3/8" 118,000 -1/4"
<br /> 16,000 14,877 24'-41/2" 1343/8- 129 3/8" 125,400 5/16"
<br /> 20,000 17,680 30'-3 3/8" 134 3/8" 129 3/8' 155,000 5/16'
<br /> 25,000 24.348 31'-71/4" 134 3/8" 129 31R" 190,000 3/8'
<br /> 30,000 27,277 36'-4 3/4" 148 143 228,000 3/8"
<br /> 40,000 32,527 49'-0" 148 143 308,000 3/8'
<br /> Sam to Spee C O l The contractor shall provide the SuperTank'The primary tank shall be
<br /> built to UL S8 construction standards with the full thickness of steel listed In Table 3.1 of UL S8.The primary
<br /> tank shall he isolated from the external environment and secondarily contained by fiberglass Reinforced
<br /> Plastic ON)mil nominal thickness)which is not attached to the tank except at the fittings.The primary tank
<br /> shalt he factory tested to 5 psi internal pressure.Prior to shipment,the annular space shall be proof tested by
<br /> vacuum only to 20"hg vacuum.The double watt tank shall have been tested In accordance with UL 1746
<br /> and shall bear an external(abet indicating that the complete tank is UL listed as a Jacketed secondary
<br /> containnipm tan4