• INDIVIDU ANK/LINE/LEAK DETECTOR T& REPORTNDE <br /> NDE ENVIRONMENTAL CORPORATION <br /> TEST DATE: April 6, 1995 WORK ORDER NUMBER: 963936 <br /> CLIENT: ULTRAKAR INC SITE: ULTRANAR 513 <br /> 'LANK tNMA?tON <br /> Tank ID: 2 Bottom to top fill in inches: 126.0 <br /> Product: SUPER Bottom to grade fill in inches: 135.0 <br /> Capacity in gallons: 12,000 Fill pipe length in inches: 32.0 <br /> Diameter in inches: 94.00 Fill pipe diameter in inches: 4.0 <br /> Length in inches: 404 Stage I vapor recovery: COAX <br /> Material: STEEL Stage II vapor recovery: ASSIST <br /> Tank: No <br /> Manifolded Vent: YES <br /> V/R: No <br /> E S I <br /> TRlK TES RESl3LT5 tK DETECTOR t3ESULTS <br /> Test method: Alert 3.000 New/passed Failed/replaced <br /> Psi at tank bottom: 1.82 detector detector <br /> Fluid level in inches: 67.50 Test method: PTA <br /> UFT/OFT UFT Make: RED JACKET RED JACKET <br /> Fluid volume in gallons: 9,226 Model: Px D.L.D. <br /> Water level in inches: 0.00 <br /> Test time: 23:21-01:52 S/N: 0202952225 101854-13 <br /> Open time in sec: 3.00 <br /> Number of thermistors: <br /> Specific gravity: 0.750 Holding psi: 19 <br /> Resiliency cc: 180 <br /> Water table depth in inches: 165.00 <br /> Test leak rate ml/min: 189.0 <br /> Determined by(method): NONTR WELL <br /> Leak rate in gph: -0.001 Metering psi: l0 <br /> RESULT: PASS Calib. leak in gph: 3.00 3.00 <br /> RESULT: PASS FAIL <br /> SNT <br /> failed at 3 and 9 <br /> ltaE TESD`IEStlt <br /> UNE EST RIWSt7aI <br /> Test method. Alert 1050 Material: FIBERGLASS <br /> Test time: 02:14-02:25 Diameter(in): 2.0 <br /> Ullage volume: 2,774 Length (ft): 60.0 <br /> Ullage pressure: 1.50 Test psi: 5o <br /> RESULT: PASS Bleedback cc: 25 <br /> DATA FOR UTS-4T ONLY: Test time(min): 30 <br /> Test 1:start time: 23:24 <br /> Time of test 1: finish psi: so <br /> Temperature: vol change cc: s <br /> Flow rate(cfh): Test 2:start time: 23:34 <br /> finish psi: so <br /> Time Of test 2: vol change cc: o <br /> Temperature: Test 3:start time: 23:44 <br /> Flow rate(cfh): finish psi: so <br /> Time of test 3: vol change cc: o <br /> Temperature: Final gph: 0.003 <br /> Flow rate(cfh): RESULT: PASS <br /> Test type:AcuRite <br /> # MI*I�TIS Pump type: PRESSURE Pump make: BENNETT <br /> 8906 WALL STREET SUITE 306 AUSTIN TEXAS 78754 512 719-4633 <br />