Laserfiche WebLink
Aft <br /> INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br /> ®Tankrpabgy <br /> TEST DATE: 01/30/04 8900 SHOAL CREEK,BUILDING 200 WORK ORDER NUMBER: 2229848 <br /> AUSTIN,TEXAS 78757(512)451-6334 <br /> CLIENT: USA PETROLEUM SITE: USA 3513 <br /> Tank ID: #2 2 Tank manifolded: No Bottom to top fill in inches: <br /> Product: UNLEADED Vent manifolded: YES Bottom to grade in inches: <br /> Capacity in gallons: 14,130 Vapor recovery manifolded: YES Fill pipe length in inches: <br /> Diameter in inches: 96.00 Overfill protection: YES Fill pipe diameter in inches: <br /> Length in inches: 456 Overspill protection: YES Stage I vapor recovery: DUAL <br /> Material: DW STEEL Installed: ATG Stage II vapor recovery: ASSIST <br /> CP installed on: <br /> COMMENTS <br /> al I <br /> PSI at tank bottom: New/passed Failed/replaced New/passed Failed/replaced <br /> Fluid level in inches: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> UFT/OFT: Make: RED JACKET <br /> Fluid volume in gallons: Model: Fx1V <br /> Tank water level in inches: S/N: 0401073575 <br /> Test time: NOT Open time in sec: 4.00 <br /> Number of thermisters: TESTED Holding psi: 21 NOT <br /> Specific gravity: Resiliency cc: 90 TESTED <br /> Water table depth in inches: Test leak rate ml/m: 189.0 <br /> Determined by(method): Metering psi: 12 <br /> Leak rate in gph: Calib. leak in gph: 3.00 <br /> Result: Results: PASS <br /> COMMENTS COMMENTS <br /> Test time: Material: DW FIBERG <br /> Ullage volume: Diameter(in): 2.0 <br /> Ullage pressure: Length(ft): 100.0 <br /> Results: Test psi: 5o <br /> Bleedback cc: 150 <br /> DATA FOR UTS-4T ONLY: Test time(min): 30 <br /> Test 1:Start time: 11:00 <br /> Time of test 1: Finish psi: 50 NOT NOT NOT <br /> Temperature: NOT Vol change cc: 0 TESTED TESTED TESTED <br /> TESTED Test 2:Start time: 11:10 <br /> Flow rate <br /> (cfh): Finish psi: 50 <br /> Time of test 2: Vol change cc: 0 <br /> Test 3:Start time: 11.20 <br /> Temperature: Finish psi: 50 <br /> Flow rate(cfh): Vol change cc: 0 <br /> Time of test 3: Final gph: 0.000 <br /> Temperature: Result: PASS <br /> Flow rate(cfh): Pump type: PRESSURE <br /> COMMENTS Pump make: RED JACKET <br /> COMMENTS Impact Valves Operational: YES <br /> IL <br /> Printed 02/03/2004 09:14 SBOWERS <br />