Laserfiche WebLink
TANKNOLOGY <br /> Stage H Vapor Recovery Test Results Form <br /> Air/Liquid Ratio Test For Vacuum Assist Systems <br /> LSitelnolbrmnation: USA 3513 401 W.KETTLEMAN LANE LODI CA.95240 <br /> r#: 2225298 Date: 02/04/2003 Technician: JEFF CONGER <br /> Product Flow Rate Calculation Air Volume Metered ^3 Ambient Conditions Corrected Final <br /> Gallons(g) Time(s) Flowrate Initial Final Volume Pressure Temp. Air Volumc Calculated A/L Ratio Results <br /> Nozzle# Product Dispensed Seconds G.P.M. Reading Reading Metered Inches Hg Degrees F (8^3) AIL Average Pass/Fail <br /> 7.530 47.60 9.5 7850.78 7852.23 1.450 1.44 <br /> 2 SUPREME 1.44 Pass <br /> 7.499 60.91 7.4 7852.27 7854.04 1.770 1.77 <br /> 7-11VA129 UNLEADE 1.77 Pass <br /> 7.505 49.03 9.2 7854.04 7855.50 1.460 1.46 <br /> 7 PLUS 1.46 Pass <br /> 7.492 60.00 7.5 7855.51 7857.29 1.780 1.78 <br /> SUPREME 1.78 Pass <br /> 7.522 53.90 8.4 7857.30 7858.94 1.640 1.63 <br /> 15-11VAIU29 UNLEADE 1.63 Pass <br /> Type of System Tested: HIRT System <br />