Laserfiche WebLink
Test Date: 16 Oct 1992 Work Order#: 960516 <br /> LEAK DETECTOR DATA <br /> �— Tank 1 Tank 2 Tank 3 Tank 4 Tank 5 Tank 6 <br /> Product: UNLEAD 92 UNLEAD 87 DIESEL <br /> Leak Detector <br /> manufacturer: REDJACKET REDJACKET REDJACKET <br /> Leak detector model: 116-030 116-030 116-030 <br /> Leak detector <br /> serial number: 40690 40690 40690 <br /> Resiliency: 210 220 225 <br /> Leak calibration: 4 4 4 <br /> Open time: 3 2 3 <br /> Element holding: 14 15 18 <br /> Metering PSI: 10 10 10 <br /> Confirm sensing of <br /> calibrate leak <br /> after keying nozzle: YES YES YES <br /> Does leak detector <br /> reset from GPH <br /> orifice?: NO NO NO <br /> Is seal/pressure <br /> relief tight (PLD <br /> only) ?: YES YES YES <br /> Pass/Fail: —� PASS PASS PASS <br />