Laserfiche WebLink
j <br />CUSTOMER: UNOCAL. <br />ADDRESS: 601 E. Kettleman <br />Lodi, CA <br />10 0 <br />DATE: 2-21-90 I.D. NO. <br />FINAL TEST RESULTS SUMMARY <br />LEAK LOKATOR RESULTS <br />SYSTEM TANK SIZE WATER LEVEL ALR RECOMMEN- <br />NO PRODUCT GALLONS DIA/MAIL INCHES INCHES GPH CONCLUSION DATIONS <br />- <br />1 SUPER U/L 10,000 95/ST <br />0 <br />150 -.015 <br />PASS <br />2 U/L 10,000 95/ST <br />0 <br />155 +.024 <br />PASS <br />3 DIESEL 10,000 95/ST <br />0 <br />150 +.007 <br />PASS <br />PRODUCT LINES <br />- HYDROSTATIC <br />PRESSURE TEST <br />RESULTS <br />SYSTEM TYPE OF PUMP POUNDS POUNDS MINUTES PRODUCT PRODUCT CONCLUSION <br />NO PRODUCT REMOTE SUCTION APPLIED HELD HELD LOSS CC's LOSS GPH /RESULT <br />1 SU U/L RJ 50 50 15 --- --- PASS <br />2 U/L RJ 50 50 15 --- --- PASS <br />3 DIESEL RJ 50 50 15 --- --- PASS <br />LEAK DETECTOR TEST <br />NO. PRODUCT FULL OPEN POSITION CLOSED FOR RESULTS <br />FOR 30 SECONDS 30 SECONDS <br />1 SU U/L 1 LTR 3 LTRS PASS <br />2 U/L 1 LTR 3 LTRS PASS <br />3 DIESEL i LTR 3 LTRS PASS <br />DETAIL OF TEST RESULTS <br />TEST <br />TIME <br />TEMPERATURE <br />ABSOLUTE <br />CHECK <br />SYSTEM TEST LEVEL <br />CLOCK DURATION LEAK RATE <br />COMPENSATION <br />LEAK RATE <br />TEST <br />NO PRODUCT NO (IN.) <br />START (HR -MIN) CC DIV CC/MIN <br />DELTA OF CC/MIN <br />CC/MIN GPH <br />YIN <br />1 SU U/L 1 150 10:00 60 4.095 20.478 +.050 +21.448 -.97 -.015 N <br />2 U/L 1 155 10:40 60 1.857 +3.599 +.005 +2.081 +1.518 +.024 N <br />3 DIESEL 1 150 11:40 60 2.563 -5.885 -.019 -5.393 -.49 -.007 N <br />*LEVEL - Inches from Tank Bottom to Test Level <br />ALR - Absolute Leak Rate (Measured Leak Rate - Temperature Compensation) in <br />Gallons Per Hour. <br />CONCLUSION - NFPA 329 criterion of +/- 0.05 GPA is used to certify tightness. <br />This is to certify that the above tank systems were tested, using the HUNTER <br />ENVIRONMENTAL SERVICES, INC. LEAK LOKATOR according to all standard operating procedures. <br />Those indicated as tight at full system meet the criterion established by the National Fire <br />Protection Association Pamphlet 329 for Precision Testing. <br />Date Test Conducted: 2-21-90 Team Manager: STEVE ANDERSON Associate: E. PRICE <br />Test Certification By: Harold DeRagon, Operations Manager <br />Hunter Environmental <br />597 Center Avenue, Suite 350 <br />Martinez, CA 94553 <br />