Laserfiche WebLink
�IpITER ENVIRONMENTAL SERVICES, I0 <br />' 18350 MT. LANGLEY STREET, SUITE 101 <br />FOUNTAIN. VALLEY, CA 92708 <br />800147-9014 800-247-2186 <br />CUSTOMER: UNOCAL <br />ADDRESS: 601 E. KETTLEMAN LANE <br />LODI, CA <br />3{{vvLrS�.l l*t <br />TEST RESULTS SUMMARY <br />FINAL TEST RESULTS <br />TEST DATE: 4/12/88 <br />LOCATION/IDENTIFICATION NO.: 6015 <br />PRODUCT LINES - HYDROSTATIC PRESSURE TEST RESULTS <br />SYSTEM <br />TYPE OF PUMP <br />------------------ <br />POUNDS <br />POUNDS <br />MINUTES PRODUCT <br />_______________ <br />LEAK <br />LOKATOR RESULTS_____________________ <br />APPLIED <br />SYSTEM <br />TANK <br />SIZE <br />NATER <br />LEVEL <br />ALR <br />50 <br />NO. <br />--------------------------------- <br />PRODUCT <br />----------------- <br />GALLONS <br />DIA/MATL <br />INCHES <br />_ INCHES ------------ <br />SPH <br />CONCLUSIONRECOMMENDATIONS_ <br />1 <br />S/U <br />10000 <br />95/ST <br />0 <br />161 <br />-.041 <br />TIGHT <br />2 <br />U/L <br />10000 <br />95/ST <br />0 <br />153 <br />-.006 <br />TIGHT <br />3 <br />DIESEL <br />10000 <br />95/ST <br />0 <br />150 <br />-.035 <br />TIGHT <br />4 <br />WASTE OIL <br />550 <br />45/ST <br />0 <br />89 <br />-.005 <br />TIGHT <br />PRODUCT LINES - HYDROSTATIC PRESSURE TEST RESULTS <br />SYSTEM <br />TYPE OF PUMP <br />------------------ <br />POUNDS <br />POUNDS <br />MINUTES PRODUCT <br />PRODUCT CONCLUSION <br />NO. PRODUCT <br />------------ ------------------------------------------- <br />REMOTE SUCTION <br />APPLIED <br />HELD____ <br />HELD LOSS CC's <br />--------------------------------- <br />LOSS GPH_____/RES''LT------- <br />1 S/U <br />RED JACKET <br />50 <br />50 <br />10 <br />PASS <br />2 UX <br />RED JACKET <br />50 <br />50 <br />10 <br />PASS <br />3 DIESEL <br />RED JACKET <br />50 <br />49 <br />10 <br />PASS <br />NOTE On suction systems, NEVER put more than 15 psi on any pump system. <br />CHECK <br />TEST <br />Y/N <br />N <br />N <br />N <br />N <br />CERTIFICATION rrD������ <br />This is to certify that the above tank systems were tested, using the HUNTER ENVIRONMENTAL SERVICES, INC. LEAK <br />LOKATOR according to all standard operating procedures. Those indicated as tight at full system meet the criterion <br />established by the National Fire Protection Association Pamphlet 329 for Precision Testing. <br />Tests'Conducted and Certified By: Test Van No. 7 <br />Team Manager: P. WHEELER <br />Tank Testing Specialist: S. ANDERSON <br />Y <br />DETAIL OF TEST RESULTS <br />>. <br />1' <br />TEST <br />TIME <br />LEAK <br />RATE TEMPERATURE <br />ABSOLUTE <br />SYSTEM <br />TEST <br />LEVEL <br />CLOCK DURATION <br />COMPENSATION <br />LEAK RATE <br />10; PRM <br />NO. <br />(IN.) <br />STATE (HR -MIN) <br />CC/DIV <br />CC/MIN DELTA of CC/MIN <br />CC/MIN <br />GPH <br />1 S/U <br />1 <br />161 <br />10:55 :60 <br />-2.098 <br />-12.512 -.023 -9.866 <br />-2.647 <br />-.041 <br />2:UX <br />1 <br />153 <br />12:05 :60 <br />-1.474 <br />-12.886 -.003 -12.490 <br />-.396 <br />-.006 <br />3 ' DIESEL <br />1 <br />150 <br />1:05' :60 <br />-2.013 <br />-1.703 +.002 +.567 <br />-2.270 <br />-.035 <br />4 WASTE OIL <br />1 <br />89 <br />8:45 :60 <br />-1.311 <br />-.695 -.067 -1.046 <br />-.351 <br />-.005 <br />,*LEVEL - <br />Inches <br />from Tank Bottom to Test <br />Level <br />ALR - <br />Absolute Leak <br />Rate (Measured Leak <br />Rate <br />- Temperature Compensation) <br />in Gallons <br />Per Hour <br />CONCLUSION - <br />NFPA 329 criterion of +/- 0.05 <br />GPA is used to certify tightness <br />CHECK <br />TEST <br />Y/N <br />N <br />N <br />N <br />N <br />CERTIFICATION rrD������ <br />This is to certify that the above tank systems were tested, using the HUNTER ENVIRONMENTAL SERVICES, INC. LEAK <br />LOKATOR according to all standard operating procedures. Those indicated as tight at full system meet the criterion <br />established by the National Fire Protection Association Pamphlet 329 for Precision Testing. <br />Tests'Conducted and Certified By: Test Van No. 7 <br />Team Manager: P. WHEELER <br />Tank Testing Specialist: S. ANDERSON <br />Y <br />1' <br />