Laserfiche WebLink
APR -15-1997 13:05 ON <br />0i► <br />tmv� 207 282 9002 P-06 <br />Monitor <br />= TS-1000EPi Tank Sentinel <br />NA -not applicable <br />Sensor <br />= TSP -EIS Standard Sensor <br />NR=no response <br />Probe Diameter <br />= 1.53 w 0.005 cm a = 0.05 <br />Minimum Sensitive <br />Height = 0.55 in (1.35 cm) + 0% = <br />0.66 in (1.67 cm) <br />TEST PRODUCT = UNLEADED GASOLINE <br />Test Distance = 7.6 meters (25 ft) <br />Liquid Response <br />Recovery <br />Product <br />Liquid__ <br />Trial# <br />Probe# Temp. Time <br />Time <br />Activation <br />Flow Date <br />Volume <br />{¢C) (min) <br />min <br />Hei ht cm <br />(mVmin. <br />mi <br />1 <br />EIS -1 20.5 3.03 <br />0.23 <br />1.50 <br />4.95 <br />15.0 <br />2 <br />EIS -1 20.5 2.93 <br />0.23 <br />1.50 <br />5.11 <br />15.0 <br />3 <br />EIS -1 20.5 3.00 <br />0.25 <br />1.50 <br />5.00 <br />15.0 <br />4 <br />Els-1 20.5 3.08 <br />0.25 <br />1.50 <br />4.86 <br />15.0 <br />5 <br />EIS -1 20.5 3.02 <br />0.23 <br />1.50 <br />4.97 <br />15-0 <br />6 <br />EIS -1 20.5 3.03 <br />0.23 <br />1.50 <br />4.95 <br />15.0 <br />Average <br />3.02 <br />0.24 <br />1.50 <br />4.97 <br />15.0 <br />S, id. Dev. <br />0.05 <br />0.01 <br />0.00 <br />0.08 <br />0.0 <br />Detection Accuracy (0/4) <br />100.0 <br />Calculated Lower Detection Limit <br />Product Activation Height (cm) <br />1.50 <br />Carnegie Mellon Research Institute 4400 Fifth Ave. Pittsburgh, <br />