bp <br /> Line Leak Detector Test Data Sheet <br /> Station # BP2093 Date 01/09/2009 <br /> Address. 3425 Tracy Blvd <br /> Tracy, CA 95376 <br /> Test Information <br /> X 2 3 4 S <br /> Product 87 91 <br /> Manufacturer VR VR <br /> Model PLLD PLLD <br /> Full Operating Pressure(psi) 34 34 <br /> Line Bleed Back (ml) 70 80 <br /> Trip Time(sec) 1:15 1:30 <br /> Metering Pressure(psi) 10 10 <br /> F/E Holding Pressure(psi) 22 24 <br /> Test Leak Rate(ml/min)(gph) 190 190 <br /> PASS or FAIL Pass Pass <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor_Tait Environmental Services <br /> Technician Steve Graham Lic# A24322 <br /> Signature <br />