SWRCB, January 2002 <br />6. PIPING SUMP TESTING <br />Page _5_ of _9_ <br />Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specie) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Sped) <br />Test Equipment Used: INCON SUMP TESTER <br />Equipment Resolution: + / - 0.002" <br />Sump # 87(1) <br />Sump # 87(2) <br />Sump # 87(3) <br />Sump # 91 <br />Sump Diameter: <br />48" <br />48" <br />48" <br />48" <br />Sump Depth: <br />62" <br />63" <br />63" <br />63" <br />Sump Material: <br />FIBERGLASS <br />FIBERGLASS <br />FIBERGLASS <br />FIBERGLASS <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />18" <br />18" <br />18" <br />20" <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />24" <br />32" <br />24" <br />24" <br />Condition of sump prior to testing: <br />DRY <br />DRY <br />DRY <br />DRY <br />Portion of Sump Tested' <br />ABOVE <br />PENETRATIONS <br />ABOVE <br />PENETRATIONS <br />ABOVE <br />PENETRATIONS <br />ABOVE <br />PENETRATIONS <br />Does turbine shut down when <br />sump sensor detects liquid (both <br />product and water)?` <br />Elves ❑ No ®NA <br />[--Ives ❑ No ®NA <br />Elves ❑ No ®NA <br />Elves ❑ No ®NA <br />Turbine shutdown response time <br />N/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail-safe <br />Yes ❑ No ®NA <br />Elves <br />Elves ❑ No ®NA <br />Elves ❑ No ®NA <br />Elves ❑ No ®NA <br />Was fail-safe verified to be <br />operational?* <br />Elves ❑ No ®NA <br />Elves ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />_ <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />10 MIN <br />10 MIN <br />10 MIN <br />10 MIN <br />Test Start Time: <br />10:36 <br />11:48 <br />11:48 <br />12:45 <br />Initial Reading (R,): <br />7.3414" <br />5.2226" <br />3.6638" <br />6.0079" <br />Test End Time: <br />10:52 <br />12:03 <br />12:03 <br />1:00 <br />Final Reading (R,:): <br />7.3415" <br />5.2225" <br />3.6638" <br />6.0079" <br />Test Duration: <br />15 MIN <br />15 MIN <br />15 MIN <br />15 MIN <br />Change in Reading (RF -R,): <br />0.0001" <br />-0.00011, <br />0.0000" <br />0.0000" <br />Pass/Fail Threshold or Criteria: <br />+/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />+/-0.002" <br />Test Result <br />0 Pass '' ❑ Fail <br />0 Pass ❑ Fail <br />® Pass ❑ Fail <br />0 Pass El Fail <br />Was sensor removed for testing? <br />®Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />®Y'es ❑ No ❑ NA <br />®Yes ❑ No El NA <br />®Yes ❑ No ❑ NA <br />®Yes ❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />ABOVE IS THE LAST OF TWO BACK TO BACK 15 MINUTE TESTS <br />FENVIRON ENTAL <br />' If the entire depth of the sump is not tested, specify how much was tested. If the answer to a� of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -160) <br />