Laserfiche WebLink
0 0 <br />bp <br />Emergency Shut -Off (ESO) Testing Results & Checklist <br />"y(k py y (:o„tr`a to Iri <br />Site # 2093 Co. Name: FASTECH <br />t 'resl'ResuIfSK <br />Date:11/28/12 <br />Addr. 3425 Tracy Blvd Phone: 714-523-0194 <br />® PASS <br />or <br />FAIL (Next Day Repair Required) <br />City/St: Tracy, CA Lead Tech: Isaac Anderson (Alltech Petro) <br />eMaint. W.O. # 9858888 Name: Isaac Anderson (Alltech Petro <br />Passport#: B36878 <br />Signature: <br />qWalliteling system circuits (turbines, and dispensers) are de - <br />The objective of this test Is to provide assurance that when the ESO switch is actlIrr <br />energized, and remain de -energized until they are re -set manually. The test procedures and guidelines shall be in accordance with the ESO Testing Process. <br /># <br />The following information is to be completed. <br />X To Select <br />Yes No N/A <br />SITE <br />Number of ESO s- 1 <br />Type of Switch Push Pull Monentary Plain light/Toggle Other: <br />if Momentary type, locate and identify re -set button): <br />Type of Turbine Control Relay System (Electrical Distribution Center): <br />9 Brown Box 9@ Power Solution 9 Custom Fabricate( Carolina Box Other <br />of Turbine Control Relays: W Make FE Petro Model ist-VFC <br />1 <br />2 <br />3 <br />4 IType <br />5 <br />X. <br />6 <br />Type of Line Leak Detection: 9 Mechanical ® ELD / CPT PLLD <br />»�< <br />Of <br />Does the ESO shutdown power to the DISPENSERS? <br />7 <br />Does the ESO shutdown power to the TURBINES? <br />8 <br />Is the 220 voltage to the turbine relay removed (either the line side or the motor side of the contacts or the <br />coil)? <br />Q <br />9 <br />Are the DISPENSER BREAKERS clearly identified / labeled? <br />Q Q <br />10 <br />Are the TURBINE BREAKERS clearly identified / labeled? <br />Q <br />11 <br />Are all the ESOs accessible and clearly identified / labeled? <br />Q Q <br />12 <br />Did the ESO(s) function correctly (de -energized from either the line side or the motor side of the contacts <br />or the coil)? <br />12A <br />If #12 is NO, briefly describe what was wrong: <br />0 <br />12B <br />How was it corrected: <br />If repair or ESO functionality cannot be corrected same day (prior to leaving the site). The technician MUST notify the <br />Site Manager of the problem, place an "Out of Service” Tag on the ESO(s), and identify an alternate mean (i.e., locate <br />circuit panel , clearly identify turbine and dispenser breakers for shut-off in the event of an emergency). <br />12C <br />Elite Customer Solution Center has been contacted for the repair. <br />12D <br />eMaint. W.O. Tick <br />� Q <br />RIM 3PY10 <br />Site's fueling system is fully operational. <br />11 <br />equipment secured and an access orts, lids, enclosures are closed. <br />All safet barricadees, and an debris was been removed."$` <br />r12All <br />,_ 't'' s h'^,, ¢�h Y%P #` ..'a. 'x" tticVc..v.4.yu. r.�i -�YO <br />. <br />Submit completed copy with other documentation in E -Maintenance. <br />