Laserfiche WebLink
s. <br />INTIRRIT'S TANK TNG SERAIE8 <br />41 WEST YOKUTS AVE. STOCKTON, CALIFORNIA 95207 <br />November 17 1992 <br />T1. fl, ?Mm <br />4, D <br />Frank's Arco <br />290 North Main Street <br />Manteca, California 95331 <br />13 <br />D E C <br />I. 8 1992 <br />Q LTH <br />Following is a summary of the precision testing we recently conducted op. <br />p -our underground storage tank(s) at the above tite. <br />Enclosed are copies of the test worksheet, graphs, and/or computer <br />generated summations for your submittal to the appropriate governmental <br />agency. <br />A tank system may be considered tight, according to the current regulaficals <br />if the test results shown below do not exceed 0.05 gph. If the result.;, are <br />beyond this parameter, an unauthorized release may have occurred, and you <br />should consider taking remedial action. <br />TANK 9 OR <br />TANK <br />PRODUCT <br />TEST <br />WfTHIN Tff;HT' <br />LOCATION <br />CAPACITY <br />CONTAINED <br />RESULTS <br />PARAMETERS <br />EastTank <br />8,000 <br />Gasoline <br />-.016 <br />Yes <br />Center Tank <br />8,000 <br />Gasoline <br />-.018 <br />Yes <br />West Tank <br />8,000 <br />Gasoline <br />+.002 <br />Yes <br />Sincerely, <br />"101 Z <br />W. N. Savage <br />A <br />TOLL FREE (800) 262-8378 <br />