Laserfiche WebLink
I t <br />Triangle Environmental, Inc.,"— "' ' ' 2003 <br />, <br />Dq <br />2525 West Burbank Blvd., Burbank, CA 91505-2302 , J,�r HILA1 TH <br />PE. 19 M L <br />(818) 840-7020 (818) 840-6929 !CFS <br />Precision Underground Storage Tank System Leak Test <br />Client: <br />Conoco Phillips Co. Facility # 255417 <br />1500 North Priest Drive <br />Tempe, AZ 85281 Test Date: 8/ 4/03 <br />Kathy Strickland <br />(602) 728-7149 30877 <br />Facility: 255417 Work #: 20001398 <br />Facility # 255417 County: SAN JOAQUIN <br />1700 EAST YOSEMITE AVE Cross Street: HVVY 99/HWY 120 <br />MANTECA, CA 95336 <br />Tank Test System Tank Line <br /># Product Capacity Type Rate/Results Ullage Result Rate/Result L/D Result <br />I Unleaded Regular 12032 System 4000 <br />2 Unleaded Premium 12032 System 4000 <br />Certified By: Technician: Tom Corcoran <br />—/—�_ Mfgr's #: TEJ-067 <br />N/A N/A N/A PASS <br />N/A N/A N/A PASS <br />State Lic. #s: 02-1626 <br />VR -7539 <br />Comments: <br />Compliance L/D, monitor certification & IF. <br />This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br />procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br />gph with a Pd >95% and Pfa <5% as required by Local, State and Federal EPA UST Technical <br />Standards Part 280 for precision testing systems. This SB -989 secondary containment testing system <br />exceeds the criteria for detection as required by state and local agencies. <br />