• <br />PUBLIC HEALTH SERVICES <br />SAN JOAQUIN COUNTY <br />ENVIRONMENTAL HEALTH DIVISION `° I <br />Karen Furst, M.D., M.P.H., Health Officer <br />304 East Weber Avenue, Third Floor • Stockton, CA 95202 <br />209/468-3420 <br />December 18, 1997 <br />Chris Guterres <br />RHL Design Group Inc. CL <br />1390 Willow Pass Road, Ste 420 <br />Concord, CA 94520 <br />RE: Proposed upgrade of an underground storage tank system <br />located at 1700 E. Yosemite Ave. Manteca, CA. <br />Conditions for approval: <br />1. The primary and secondary piping must undergo the testing <br />criteria of PHS-EHD, as indicated on installation plan <br />application. <br />2. All containment sumps must undergo the lake sump test <br />criteria of PHS-EHD, as indicated on the installation plan <br />application. <br />3. In order for the facility to receive the exemption from the <br />annual line test the pump system must demonstrate positive <br />automatic shut -down. The monitoring system must be able to <br />kill the turbine when the probe senses a leak, malfunctions <br />or when any part of the monitoring system is disconnected. <br />4. Tanks and lines must tested for tightness using a State <br />approved method. The test must be conducted by a licensed <br />tank tester. <br />5. Any portion of the product piping that is damaged or <br />removed are subject to closure requirements prior to being <br />repaired or replaced. <br />Karen Furst, M.D., M.P.H. <br />Health Office <br />Robert McClellon, Sr. R.E.H.S. <br />Environmental Health Division <br />A Division of San Joaquin County Health Care Services <br />