Laserfiche WebLink
TANKN�LOGY - UNDERGROUND <br />�}ETECTION SYSTEM <br />- (V3.120�� Page 8 <br />SHELL OIL CO <br />HUU9204-lVE341130-48290-01 - Apr N, 1992/ 23:52 <br />���-T- <br />01.1 r-141 F"- lhul <br />`TEST DATE <br />Apr 14, 1992 <br />START TIME <br />: 23:52:14 <br />CLIENT <br />: SHELL OIL CO <br />LOCATION NAME <br />: SHELL OIL CO <br />LOCATION CODE <br />: 2046522030 <br />TANK CONFIGURATION <br />: Tandem <br />TANK CONTENTS <br />: SUN, 8RUN <br />TANK NUMBER <br />TANK DIAMETER <br />: 95 <br />95 in <br />TANK CAPACITY <br />: 8000 <br />8000 S <br />TANK MANUFACTURER <br />: <br />TANK MATERIAL <br />: Steel <br />Steel <br />TANK REGISTRATION # <br />: <br />TANK DATE INSTALLED <br />INITIAL DIPPED �UEL LEVEL <br />: 64.00 <br />66.00 in <br />INITIAL DIPPED WATER LEVEL <br />: 0.00 <br />0.00 in <br />POST PUMPINS WATER LEVEL <br />in <br />-�....... ..... <br />jK_-� <br />TEST INITIAL WATER LEVEL <br />: 0.00 <br />0.00 in <br />TEST FINAL WATER LEVEL <br />: 0.00 <br />0.00 in <br />WATER INGRESS <br />: 0.00 <br />0.00 in <br />BUBBLE SIGNATURES <br />VACU-TECT TEST RESULT <br />: Passed <br />Passed <br />COMMENTS: <br />CONCLUSION: TANKS 44--1 AND 44:2 TESTED TIGHT. <br />LINE <br />#1 Passed <br />#2 <br />#3 <br />#4 <br />COMMENTS: <br />TEST RATE <br />50 PSI 0.00 GPH Passed <br />CONCLUSION: LINES 1A AND 2A TESTED TIGHT. <br />TEST RATE <br />50 PSI 0.00 GPH <br />This test was cond.v-41md * arcordance with U.S. BA Rule 40 CFR Pants 280 and 281. <br />VA0EN BODILY ' � VACU-TECT(tm) Test Number <br />