Laserfiche WebLink
INDIVIDU&ANK/LINE/LEAK DETECTOR To REPORTNDE <br /> NDE ENVIRONMENTAL CORPORATION <br /> TEST DATE: December 1, 1994 WORK ORDER NUMBER: 963222 <br /> CLIENT TOSCO NOR ST COMPANY SITE: BP 1-1195 <br /> Tank ID: 3 Bottom to top fill in inches: 129.0 <br /> Product: REG UNLEAD Bottom to grade fill in inches: 136.0 <br /> Capacity in gallons: 10,000 Fill pipe length in inches: 37.0 <br /> Diameter in inches: 92.00 Fill pipe diameter in inches: 4.0 <br /> Length in inches: 352 Stage I vapor recovery: COAX <br /> Material: FIBERGLASS Stage II vapor recovery: BALANCE <br /> Tank: No <br /> Manifolded Vent: No <br /> V/R: No <br /> TtdKTEST ftEStJLTt3 LEAK DETECT flR RESULTS <br /> Test method: Alert 4000 New/passed Failed/replaced <br /> Psi at tank bottom: 1.88 detector detector <br /> Fluid level in inches: 70.00 Test method: FTA <br /> UFT/OFT: uFT Make: RED JACKET RED JACKET <br /> Fluid volume in gallons: 8,166 Model: X.L.D. D.L.D. <br /> Water level in inches: 0.00 S/N: 103940341 11290---- <br /> Test time: 21:42-02:14 Open time in sec: 3.00 <br /> Number of thermisters: Holding psi: 14 <br /> Specific gravity: 0.745 Resiliency cc: 160 <br /> Water table depth in inches: 160.00 Test leak rate ml/min: 189.0 <br /> Determined by(method): NONTR WELL Metering psi: 10 <br /> Leak rate in gph: -0.029 Calib. leak in gph: 3.00 3.00 <br /> RESULT: PASS RESULT: PASS FAIL <br /> C# ±tMEt�tTS . : 0.,W sAENTS <br /> failed at 3 and 6 <br /> lJL1J�GE TEST RES1fLTS LINE TEST RESt3LTS <br /> Test method: Alert 1050 Material: FIBERGLASS <br /> Test time: 02:37-02:49 Diameter(in): 2.0 <br /> Ullage volume: 1,834 Length (ft): 70.0 <br /> Ullage pressure: 1.50 Test psi: 5o <br /> RESULT: PASS Bleedback cc: 130 <br /> DATA FOR UTS-4T ONLY: Test time(min): 30 <br /> Time of test 1: Test 1:start time: 23:15 <br /> finish psi: so <br /> Temperature: vol change cc: 15 <br /> Flow rate(cfh): Test 2:start time: 23:25 <br /> Tifinish psi: so <br /> Time of test 2: <br /> vol change cc: 5 <br /> Temperature: Test 3:start time: 23:35 <br /> Flow rate(cfh): finish psi: so <br /> Time of test 3: vol change cc: o <br /> Temperature: Final gph: 0.011 <br /> Flow rate(cfh): RESULT: PASS <br /> Test type:AcuRite <br /> MENTS Pump type: PREssuRE Pump make: RED JACKET <br /> 0. < S <br /> 8906 WALL STREET SUITE 306 AUSTIN,TEXAS 78754 512 719-4633 <br />