Laserfiche WebLink
Triangle Environmental, Inc. <br /> SYSTEMS TANK, LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Tosco Facility # 30225 <br /> Tank #: 3 Test Date: 6/ 2/98 <br /> Product: Unleaded Regular Work#: 460340 <br /> X.:. . ........ <br /> . ............... <br /> Test Method: System 5000 Test Method: R.J. FTA <br /> Capacity: 9528 Manufacturer: Vaporless <br /> Diameter(in): 92 L/D Model: LD2000 <br /> Product Level(in): 50 L/D Serial#: 46999 <br /> Liquid Volume(Gals): 5438 Line Drain Back(ml): 100 <br /> Liquid Percent(%): 57.1% L/D Trip Time(sec): 2 <br /> Specific Gravity: 0.750 Holding Pressure(psi): 27 <br /> Coef. of Expansion: 0.000600 Metering Pressure(psi): 23 <br /> Water On Tank(in): 40 L/D Test Rate(gph): 1.4 <br /> Water In Tank(in): 0 L/D Result: PASS <br /> Product Temp. (F): 70 New Leak Detector? No <br /> Head Pressure(psi): -0.1 ilgg. <br /> W.-T....-ii-A M- 011:11;11111SI <br /> ............. <br /> ................ <br /> Test Start Time: 7:00 PM ............... <br /> Test End Time: 7:15 PM Test Method: TEI LT-3 <br /> Test Rate(gph): 0.010 Pump Brand: Red Jacket <br /> Test Result: PASS System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 10:00 PM <br /> Test Method: ULLAGE Line End Time: 10:15 PM <br /> UllageVolume(gals.): 4090 Line Start Level: 140 <br /> Ullage Test Time: 7:00 PM Line End Level: 130 <br /> Ullage Vacuum(psi): 0.4 Line Test Rate(gph): -0.011 <br /> Ullage Result: PASS Line Test Result: PASS <br /> X %XV.4. X <br /> ....... . ...... ...... <br /> ..... ... ..... <br /> .... ......... ... . ................ .... ...... <br /> ............................. <br /> ........ . ... <br /> 4 <br />