Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: Circle K #30225 <br /> Tank : 1 Test Date: 8/18/97 <br /> Product: Unleaded Plus Work#: 460119 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: 7632 Manufacturer: Vaporless <br /> Diameter(in): L/D Model: id-2000 <br /> Product Level(in): L/D Serial#: 46018 <br /> Liquid Volume(Gals): Line Drain Back(ml): 150 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 14 <br /> Coef.of Expansion: Metering Pressure(psi): 28 <br /> Water On Tank(in): L/D Test Rate(gph): 1.7 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): <br /> Test Start Time: <br /> Test End Time: Test Method: TEI LT-3 <br /> Test Rate(gph): Pump Brand: Red Jacket <br /> Test Result: N/A System Type: Pressure <br /> Line Pressure(psi): 50 <br /> Line Start Time: 8:00:00 PM <br /> Test Method: ULLAGE Line End Time: 8:15:00 PM <br /> 7UIlageVolume(gals.): Line Start Level: 210 <br /> Line End Level: 210 <br /> Ullage Test Time: <br /> Ullage Vacuum(psi): Line Test Rate(gph): 0.000 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 2 <br />