711 <br /> Triangle Environmental, Inc. OCT 15 2002 <br /> 2525 West Burbank Blvd.,Burbank,CA 91505-2302 jViR11VIENT HEALTH <br /> (818)840-7020 (818)840-6929 EERNIIT/SERVICES <br /> UST TESTING SYSTEMS SUMMARYSHEET <br /> Precision Underground Storage Tank System Leak Test <br /> Client: <br /> Phillips 66 Company Tosco Corp. Facility # 30225 <br /> 1500 North Priest Drive <br /> Tempe, AZ 85281 Test Date: 9/23/02 <br /> Kathy StrickLand <br /> (602)728-7149 <br /> Facility: 2611195 Work#: 12901074 <br /> Tosco Corp. Facility#30225 County: SAN JOAQUIN <br /> 16500 LOUISE Cross Street: SEQ LOUISE&I-5 <br /> LATHRUP, CA 95209 <br /> Tank Test System Tank Line <br /> # Product Capacity Type Rate/Results Ullage Result Rate/Result L/D Result <br /> 1 Unleaded Regular 11849 N/A N/A -0.005 PASS PASS <br /> 2 Unleaded Premium 11849 N/A N/A 0.000 PASS PASS <br /> Certified By: Technician: Tom Corcoran State Lic.#s: 02-1626 <br /> �� Mfgr's#: TEI-067 <br /> VR-7539 <br /> Comments: <br /> Compliance P-L/TST&incomplete monitor certification witnesed by Dina Abate of the County of San <br /> Joaquin Environmental Health Department. Stage II A/L and Grounding. <br /> This precision tank testing system has been third party evaluated according to the guidelines of the EPA <br /> procedures for annual leak detection systems and found to exceed the criteria of detecting a leak of 0.10 <br /> gph with a Pd>95% and Pfa<5% as required by Local,State and Federal EPA UST Technical <br /> Standards Part 280 for precision testing systems. This SB-989 secondary containment testing system <br /> exceeds the criteria for detection as required by state and local agencies. <br />