Laserfiche WebLink
Monitoring System Certification <br /> D. Results of Testing/Servicing <br /> Software Version Installed: 16.05 <br /> Complete the following checklist: <br /> 0 Yes ❑ No* Is the audible alarm operational? <br /> 0 Yes ❑ No* Is the visual alarm operational? <br /> ❑ Yes 0 No* Were all sensors visually inspected,functionally tested,and confirmed operational? <br /> 0 Yes ❑ No* Were all sensors installed at lowest point of secondary containment and positioned so that other equipment will <br /> not interfere with their proper operation? <br /> 0 Yes ❑ No* If alarms are relayed to a remote monitoring station, is all communications equipment (e.g. modem) <br /> ❑ N/A operational? <br /> DYes ❑ No* For pressurized piping systems, does the turbine automatically shut down if the piping secondary containment <br /> ❑ N/A monitoring system detects a leak,fails to operate,or is electrically disconnected? If yes:which sensors initiate <br /> positive shut-down? (Check all that apply) 0 Sump/Trench Sensors; 0 Dispenser Containment Sensors. <br /> Did you confirm positive shut-down due to leaks and sensor failure/disconnection? 0 Yes; ❑No. <br /> ❑ Ye ❑ No* For tank systems that utilize the monitoring system as the primary tank overfill warning device (i.e. no <br /> 0 N/A mechanical overfill prevention valve is installed), is the overfill warning alarm visible and audible at the tank <br /> fill point(s)and operating ro erl ? If so,at what percent of tank capacity does the alarm trigger? _% <br /> ❑ Yes* ❑D No Was any monitoring equipment replaced? If yes,identify specific sensors,probes,or other equipment replaced <br /> and list the manufacturer name and model for all replacement parts in Section E,below. <br /> ❑Yes* 0 No Was liquid found inside any secondary containment systems designed as dry systems? (Check all that apply) <br /> ❑Product; ❑ Water. If yes,describe causes in Section E,below. <br /> 0 Yes I ❑ No* I Was monitoring system set-up reviewed to ensure proper settings?Attach set up reports,if applicable <br /> ❑ Yes I 0 No* I Is all monitoring equipment oerational per manufacturer's specifications? <br /> *In Section E below,describe how and when these deficiencies were or will be corrected. <br /> E. Comments: The 87 Annular Sensor was not removable for testing. Apparently, the <br /> extra pressure on the annular space when the tank has a high fuel level, traps the sensor in place. <br /> We will have to wait until the fuel level is lower, when the sensor is loose, so that the sensor operation <br /> can be tested. <br /> The monitor printer paper feed device is not operating properly. A new printer will be installed. <br /> 2. Monitor lamps are burned out - will replace. <br /> UN-036-2/4 Page 2 of 4 Rev.06/04/01 <br /> www.unidocs.org <br />