Laserfiche WebLink
C-- aMF' I ISEMCE IJST SE R V I CIES.* IMC. <br />417 MQNTCL_A Z R 07 RaK7 CA 93309 4 000 D i s 1 —3070 <br />AES/System II Precision leak Test Graph (OverFill) <br />Invoice No.1 2279 Dates 07/11/96 Time 1 07:23:21 <br />Technicians DMv Tank1 3 Tank Diameter(in)s 65 <br />Volume(gal)s 3000 Grade Llvel(in)1 96 Product Level(in)s 93 <br />Water Level On Tank(in)s 0 <br />Specific Gravity) .75 Coefficient Of Expansions 0.0006689 <br />Calibration Value(ml)1 200 Channels 3 <br />Level Segment Froms 1 To 250 Temp Segment Frome i To 250. <br />P' h" r rj 1-1 r- isPLUS <br />L <br />E501 I <br />V <br />L dry <br />TO a Mac= <br />lµl 1 3 0 2'D <br />Ti rr'rr —Hour :: <br />Change In Calibration Zone m 49 <br />Starting Temperature (F)1 59.155 <br />Surface Area(sq. in) 1 24.9 <br />Level volume (gph) 1 0.01 <br />Temp. volume (gph) s 0.02 <br />Net change (gph) 1 —0.01 <br />mmmommmmmm <br />Flea s Ut 1't; --> P'ASS <br />Copyright (c) 1989 by AES, Inc. <br />** Notes ** <br />Calibration Unit (pal/unit) • 0.00'108 <br />Head Pressure(psi (Btm)) s 2.52 <br />Temp. Change (F/h) 1 0.014 <br />Product Line(gph)s SUCTION <br />MBP., 983 MOFFAL BLVD. , MANTECA, CA. <br />THIS IS A HIGH LEVEL TEST WITH A 200 ML. CALIBRATION. <br />THE PRODUCT LINE IS FLOODED AND INCLUDED IN THESE DATA. <br />